Configuring Terminals 9 & 10 (Digital Input/Output); Pid - Tuning Your Drive - Parker 650G Product Manual

Frame 1, 2, 3 & c - f
Hide thumbs Also See for 650G:
Table of Contents

Advertisement

6-13
Programming Your Application
Configuring Terminals 9 & 10 (Digital Input/Output)
Terminal 10 can be operated as digital input DIN 4 or digital output DOUT2. It is configured
via the keypad or DSE (or other suitable programming tool). The default for terminal 10 is to
operate as a digital input, and the input logic is non-inverted.
Terminal 9 can be operated as digital input DIN3 or digital output DOUT1, however, it can only
be configured via DSE (or other suitable programming tool). The default for terminal 9 is to
operate as a digital input, and the input logic is non-inverted.
Configure for use as a Digital Input (default)
For example, to use terminal 10 as an input, the output circuitry must be disabled by setting
S
Configure for use as a Digital Output
For example, to use terminal 10 as an output, select
you could set parameter
running, operating an external relay or lamp. You can invert this logic using parameter

PID - Tuning Your Drive

Parameters
used specifically in system applications involving the control of drives to provide zero steady
state error between Setpoint and Feedback, together with good transient performance.
Proportional Gain (
This is used to adjust the basic response of the closed loop control system. The PI error is
multiplied by the Proportional Gain to produce an output.
S
OP21 and
OP22 to zero. You can invert this logic using parameter
Parameter
DOUT2 SOURCE
DOUT2 INVERT
DIN4 INVERT
S
OP21 to 3 to have the output go high (24V) whenever the motor is
Parameter
DOUT2 SOURCE
DOUT2 INVERT
P
P
501 to
508: PID is used to control the response of any closed loop system. It is
P
501)
www.comoso.com
Setting
0
0
Default is 0, setting to 1 inverts the input logic
S
OP21 to be 1, 2, 3, 4 , 5 or 6. For instance,
Setting
The output is high when:
1 = HEALTH
The Run signal is not present, or no
trip is active
2 = TRIPPED
A trip is present
3 = RUNNING
The motor is running
4 = AT ZERO
The output frequency is below 1% of
MAX SPEED (
5 = AT SPEED
The output frequency is at or near
Setpoint and within ±1% of MAX
SPEED, set by (P2). For example:
if MAX SPEED = 50Hz and Setpoint
= 30Hz, then 1% of MAX SPEED =
0.5Hz. So AT LOAD is True
between 30 ±0.5Hz.
6 = AT LOAD
The magnitude of the output torque
is greater than or equal to the
torque level set in
Always set
S
IP04 to 0 if using Applications 1 and 5 –
refer to Chapter 12.
Default is 0, setting to 1 inverts the output logic
S
IP04.
S
OP22.
P
2)
S
ST42
650G AC Drive

Advertisement

Table of Contents
loading

Table of Contents