Parker 650G Product Manual page 146

Frame 1, 2, 3 & c - f
Hide thumbs Also See for 650G:
Table of Contents

Advertisement

13-5
Applications
Application 2: Auto/Manual Control
Two Run inputs and two Setpoint inputs are provided. The Auto/Manual switch selects which pair of inputs is active.
The Application is sometimes referred to as Local/Remote.
SINGLE
WIRE
STARTING
Auto
Setpoint
A or V
Manual
Setpoint
default source
= 4 - 20mA
User Relay
Control
Terminal
13
DIN7 (ENCB)
not used
12
DIN6 (ENCA)
not used
11
DIN5
NOT COAST STOP
10
DIN4/DOUT2
REMOTE REVERSE 0V = remote forward, 24V = remote reverse
9
DIN3
SELECT
8
DIN2
AUTO RUN
7
DIN1
MANUAL RUN
6
+24V
24V
5
AOUT
RAMP OUTPUT
4
+10V REF
+10V REF
3
AIN2
AUTO SETPOINT
2
AIN1
MANUAL SETPOINT
1
0V
0V
RL1A
DOUT3 (relay)
RELAY SOURCE
RL1B
www.comoso.com
24V = coast to stop, 0V = drive may run
24V = run forward
24V = run forward
24V = run forward
= 1
DEMAND (0V = 0%, 10V = 100%)
= 3
4mA = 0%, 20mA = 100%
= 0
0V = 0%, 10V = 100%
= 1
HEALTH i.e. 0V = not healthy
650G AC Drive

Advertisement

Table of Contents
loading

Table of Contents