5.10 o: Operator Related Settings
No.
o4-07
n
o4-09: IGBT Maintenance Setting
Sets the value of the IGBT maintenance time displayed in U4-07 as a percentage of the total expected performance life. This
value should be reset to 0 when the IGBTs have been replaced.
Note:
The actual maintenance time depends on the environment the drive is used in.
No.
o4-09
n
o4-11: U2, U3 Initialization
When the drive is initialized, the fault trace and fault history monitors (U2-oo and U3-oo) are not reset. Parameter o4-11
can be used to initialize them.
No.
o4-11
Setting 0: No Action
The drive keeps a record of the fault trace and fault history.
Setting 1: Reset Fault Data
Resets the data for the U2-oo and U3-oo monitors. Once o4-11 is set to 1 and the ENTER key is pressed, the fault data
are erased and the display returns to 0.
n
o4-12: kWh Monitor Initialization
The kWh monitors U4-10 and U4-11 are not initialized when the power is cycled or the drive is initialized. o4-12 can be used
to manually reset them.
No.
o4-12
Setting 0: No Action
The kWh data are kept as they are.
Setting 1: Reset kWh Data
Resets the kWh counter. The monitors U4-10 and U4-11 will show 0. Once o4-12 is set to 1 and the ENTER key is pressed,
the kWh data are erased and the display returns to 0.
n
o4-13: Number of Run Commands Counter Initialization
The Run command counter displayed in U4-02 is not reset when the power is cycled or the drive is initialized. Using o4-13
it can be manually reset to 0.
No.
o4-13
Setting 0: No Action
The Run command data are kept as they are.
Setting 1: Reset Run Commands Counter
Resets the Run commands counter. The monitor U4-02 will show 0. Once o4-13 is set to 1 and the ENTER key is pressed,
the counter value is erased and the display returns to 0.
u

q: DriveWorksEZ Parameters

n
q1-01 to q6-07: Reserved for Use by DriveWorksEZ
These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.
252
Name
DC Bus Pre-charge Relay Maintenance Setting
Name
IGBT Maintenance Setting
Name
U2, U3 Initialization
Name
kWh Monitor Initialization
Name
Number of Run Commands Counter Reset
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Setting Range
0 to 150%
Setting Range
0 to 150%
Setting Range
0 or 1
Setting Range
0 or 1
Setting Range
0 or 1
Default
0%
Default
0%
Default
0
Default
0
Default
0