<2> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330.
<3> Range upper limit is dependent on parameter E4-01 Motor 2 Rated Current.
<4> Default setting value is dependent on parameter E5-01, Motor Code Selection.
<5> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control.
<6> Default setting value is dependent on parameter o2-04, Drive Model Selection.
<7> Parameter ignored when E1-11, Motor 1 Mid Output Frequency 2, and E1-12, Motor 1 Mid Output Frequency Voltage 2, are set to 0.0.
<8> When setting motor parameters, the motor rated current must be set to a value greater than the motor no-load current (E2-01 > E2-03).
<9> Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units.
2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units.
<10> Default setting value is dependent on parameter o2-04, Drive Model Selection and C6-01, Drive Duty Selection.
<11> Setting range becomes 0.00 to 130.00 for drives 0.2 kW and smaller.
<12> Default setting depends on the control mode for motor 2 set in parameter E3-01. The given value is for V/f Control.
<13> Parameter ignored when E3-11, Motor 2 Mid Output Frequency 2, and E3-12, Motor 2 Mid Output Frequency Voltage 2, are set to 0.
<14> Parameter can be changed during Run.
<15> If using a Yaskawa SMRA Series SPM Motor, the default setting is 1800 r/min.
<16> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06 ≠ 0.
<17> Default setting is determined by drive software version.
PRG: 1018 and later: 0.0 to 6500.0 mV/(r/min)
PRG: 1017 and earlier: 0.0 to 2000.0 mV/(r/min)
<18> Available in drive software versions PRG: 1022 and later.
u

F: Options

F parameters are used to program the drive for PG feedback and to function with option cards.
No.
Name
Operation Selection at PG
F1-02
Open Circuit (PGo)
Operation Selection at
F1-03
Overspeed (oS)
Operation Selection at
F1-04
Deviation
F1-08
Overspeed Detection Level
Overspeed Detection Delay
F1-09
Time
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Description
F1: V/f Control with Simple PG Feedback - PG Setup Parameters
Use F1 parameters to set up the drive for V/f Control with Simple PG Feedback.
These parameters are enabled only when H6-01 = 03
Sets stopping method when a PG open circuit fault (PGo)
occurs. Refer to parameter F1-14.
0: Ramp to Stop - Decelerate to stop using the active
deceleration time.
1: Coast to Stop
2: Fast-stop - Decelerate to stop using the deceleration time in
C1-09.
3: Alarm only - Drive continues operation.
Sets the stopping method when an overspeed (oS) fault occurs.
Refer to F1-08 and F1-09.
0: Ramp to stop - Decelerate to stop using the active
deceleration time.
1: Coast to stop
2: Fast-stop - Decelerate to stop using the deceleration time in
C1-09.
3: Alarm Only - Drive continues operation.
Sets the stopping method when a speed deviation (dEv) fault
occurs. Refer to F1-10 and F1-11.
0: Ramp to stop - Decelerate to stop using the active
deceleration time.
1: Coast to stop
2: Fast-stop - Decelerate to stop using the deceleration time in
C1-09.
3: Alarm only - Drive continues operation.
Sets the speed feedback level which has to be exceeded for the
time set in F1-09 before an oS fault will occur.
Set as a percentage of the maximum output frequency (E1-04).
Sets the time in seconds for which the speed feedback has to
exceed the overspeed detection level F1-08 before an oS fault
will occur.
B.2 Parameter Table
Control
Mode
Range
Def.
O
V/
P
L
f
M
V
0 to 3
1
A
0 to 3
1
A
0 to 3
3
A
0 to 120 115% A
0.0 to 2.0
1.0
A
Addr.
Pg.
Hex
381
181
382
181
383
181
B
387
181
388
181
371