5.7 H: Terminal Functions
Setting 1: Zero Speed
Terminal closes whenever the output frequency falls below the minimum output frequency set to E1-09.
Status
Open
Output frequency is above the minimum output frequency set to E1-09
Closed
Output frequency is less than or equal to the minimum output frequency set to E1-09
Setting 2: Speed Agree 1 (f
Closes whenever the actual output frequency is within the Speed Agree Width (L4-02) of the current frequency reference
regardless of the direction.
Status
Open
Output frequency does not match the frequency reference while the drive is running.
Closed
Output frequency is within the range of frequency reference ± L4-02.
Note:
Detection works in both directions, forward and reverse.
Speed agree 1
Refer to L4-01/02: Speed Agreement Detection Level and Detection Width on page 227
width.
Setting 3: User Set Speed Agree 1 (f
Closes whenever the actual output frequency and the frequency reference are within the Speed Agree Width (L4-02) of the
programmed Speed Agree Level (L4-01).
196
OFF
ON
Run command
Baseblock
OFF
command
Output
frequency
OFF
ON
During Run
Figure 5.55 During Run Time Chart
Output frequency
or
motor speed
OFF
Zero Speed
Figure 5.56 Zero-Speed Time Chart
/f
Agree 1)
ref
out
Frequency
reference
Output
frequency
OFF
ON
Figure 5.57 Speed Agree 1 Time Chart
/f
Agree 1)
ref
set
ON
Description
E1-09 (Max. Output Frequency)
ON
Description
L4-02
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
L4-02
for details on setting the detection