Table 5.4 Enter the Password to Unlock Parameters (continuing from step 4 above)
1.
Press
to enter the parameter setup display.
2.
Press
to select the flashing digits as shown.
3.
Press
to scroll to A1-04.
4.
Enter the password "1234".
5.
Press
to save the new password.
6.
Drive returns to the parameter display.
7.
Press
and scroll to A1-01.
Press
to display the value set to A1-01. If the first "0" blinks, parameter settings
8.
are unlocked.
9.
Use
and
to change the value if desired. This is not typical.
Press
to save the setting, or
10.
changes.
11.
The display automatically returns to the parameter display.
Note:
Parameter settings can be edited after entering the correct password. Performing a 2-Wire or 3-Wire initialization resets the password to
"0000". Reenter the password to parameter A1-05 after drive initialization.
n
A1-06: Application Presets
Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these
Application Presets automatically sets the required parameters to default values and selects I/Os. In addition, Application
Preset parameters are assigned to the list of User Parameters, A2-01 through A2-16. These can be accessed in the Setup Mode
and provide quicker application adjustment by eliminating the need to scroll through multiple menus.
Refer to Application Selection on page 96
n
A1-07: DriveWorksEZ Function Selection
DriveWorksEZ is a software package that can be used to customize the drive functionality or add PLC functionality by the
interconnection and configuration of basic software function blocks. The drive performs program created by the user in 2 ms
cycles.
Parameter A1-07 can be used to enable or disable the DriveWorksEZ program inside the drive.
Note:
1. If DriveWorksEZ assigned functions to any multi-function output terminals, those functions stay set after disabling DriveWorksEZ.
2. Reinitialization using A1-03 does not reset A1-07 to the factory default value.
3. For more information on DriveWorksEZ, contact a Yaskawa representative or the Yaskawa sales department directly.
No.
A1-07
Setting 0: DWEZ Disabled
Setting 1: DWEZ Enabled
Setting 2: Digital Input
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Step
to return to the previous display without saving
for details on parameter A1-06.
Parameter Name
DriveWorksEZ Function Selection
5.1 A: Initialization
Display/Result
"01" flashes
Setting Range
0 to 2
5
Default
0
119