b2-02: DC Injection Braking Current
Sets the DC Injection Braking current as a percentage of the drive rated current. If set to larger than 50%, the carrier frequency
is automatically reduced to 1 kHz.
No.
b2-02
The level of DC Injection Braking current affects the strength of the magnetic field attempting to lock the motor shaft.
Increasing the current level will increase the amount of heat generated by the motor windings. This parameter should only be
increased to the level necessary to hold the motor shaft.
n
b2-03: DC Injection Braking Time at Start
Sets the time of DC Injection Braking at start. It can be used to stop a coasting motor before restarting it or to apply a braking
torque at start. Disabled when set to 0.00 s.
No.
b2-03
Note:
Before starting an uncontrolled rotating motor (e.g. a fan motor driven by windmill effect), DC Injection or Speed Search should be used
to either stop the motor or detect its speed before starting it. Otherwise motor stalling and other faults can occur.
n
b2-04: DC Injection Braking Time at Stop
This parameter works in combination with b2-01, and sets the DC Injection Braking time at stop. Used to completely stop a
motor with high inertia load after ramp down. Increase the setting if the motor tends to coast by inertia after a stop.
No.
b2-04
n
b2-08: Magnetic Flux Compensation Value
Sets the magnetic flux compensation as a percentage of the no-load current value (E2-03) and can be used to increase the
motor flux when the motor is started up.
No.
b2-08
This parameter allows the magnetizing motor flux to be boosted when starting the motor and thereby facilitate a quick ramp-
up of the torque reference and magnetizing current reference in order to reduce motor slip during start. This flux level will be
applied below the minimum output frequency set to E1-09 until the DC Injection time at start (b2-03) expires. It may be used
to compensate for reduced starting torque due to motor circuit inefficiencies.
n
b2-12: Short Circuit Brake Time at Start
Short-Circuit braking can be used in Open Loop Vector for PM motors. By shorting all three motor phases it produces a braking
torque in the motor and can be used to stop a coasting motor before starting it.
Parameter b2-12 sets the time for Short-Circuit Brake operation at start. Disabled when set to 0.00 s.
No.
b2-12
n
b2-13: Short Circuit Brake Time at Stop
The Short-Circuit braking described for parameter b2-12 can also be applied at the end of deceleration in order to completely
stop high inertia loads. Short circuit braking is initiated when the output frequency falls below the higher of the values b2-01
and E1-09.
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
output
frequency
Figure 5.10 DC Injection Braking during Deceleration
Name
DC Injection Braking Current
Name
DC Injection Braking Time at Start
Name
DC Injection Braking Time at Stop
Name
Magnetic Flux Compensation Value
Name
Short Circuit Brake Time at Start
DC Injection Braking
start frequency
b2-01
braking time
b2-04
Setting Range
0 to 75%
Setting Range
0.00 to 10.00 s
Setting Range
0.00 to 10.00 s
Setting Range
0 to 1000%
Setting Range
0.00 to 25.50 s
5.2 b: Application
Default
50%
Default
0.50 s
Default
0.50 s
Default
0%
5
Default
0.00 s
129