5.5

E: Motor Parameters

E parameters cover V/f pattern and motor data settings.
u

E1: V/f Characteristics

n
E1-01: Input Voltage Setting
Set the input voltage parameter to the nominal voltage of the AC power supply. This parameter adjusts the levels of some
protective features of the drive (overvoltage, Stall Prevention, etc.).
NOTICE: Set parameter E1-01 to match the input voltage of the drive. Drive input voltage (not motor voltage) must be set in E1-01 for the
protective features of the drive to function properly. Failure to comply could result in improper drive operation.
No.
<1>
E1-01
<1> The setting range and default value shown here are for 200 V class drives. Double this for 400 V class units.
E1-01 Related Values
The input voltage setting determines the over-/undervoltage detection level and the operation levels of the braking transistor
as well as the KEB function and the overvoltage suppression function.
Setting Value of
Voltage
E1-01
200 V Class
all settings
setting ≥ 400 V
400 V Class
setting < 400 V
Note:
The braking transistor operation levels are valid for the drive internal braking transistor. If an external CDBR braking chopper is used, refer
to the instruction manual of that unit.
n
V/f Pattern Settings
The drive utilizes a set V/f pattern to determine the appropriate output voltage level for each relative to the frequency reference.
There are 15 different preset V/f patterns to select from with varying voltage profiles, saturation levels (frequency at which
maximum voltage is reached), and maximum frequencies. Additionally, one custom V/f pattern can be set up by programming
parameters E1-04 through E1-10.
V/f Pattern Setup for V/f Control
1.
Set the input voltage for the drive.
2.
Set the V/f pattern by:
a) choosing one of the 15 preset V/f patterns (E1-03 = 0 to E).
b) select the custom V/f pattern (E1-03 = F, default setting).
3.
When using one of the 15 presets, E1-04 through E1-13 are automatically set. Refer to the description below.
For a custom V/f pattern, E1-04 through E1-13 must be adjusted manually.
E1-13 on page
172.
Open Loop Vector Control Setup for IM and PM Motors
In OLV only the user defined V/f pattern can be used.
n
E1-03: V/f Pattern Selection
This parameter can only be changed when the drive is operating in V/f Control. It allows the user to select the V/f pattern from
15 predefined patterns or to create a custom V/f pattern.
No.
E1-03
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Parameter Name
Input Voltage Setting
ov Detection
BTR Operation
Level
Level
410 V
394 V
820 V
788 V
740 V
708 V
Refer to E1-01: Input Voltage Setting on page
Refer to V/f Pattern Settings E1-04 to E1-13 on page
Parameter Name
V/f Pattern Selection
Setting Range
155 to 255 V
(Approximate Values)
Desired DC Bus
Uv Detection Level
Voltage during KEB
(L2-05)
(L2-11)
190 V
(single-phase = 160
V)
380 V
350 V
Refer to V/f Pattern Settings E1-04 to
Setting Range
0 to F

5.5 E: Motor Parameters

Default
230 V
ov Suppression /
Stall Prevention
Level
(L3-17)
240 V
370 V
480 V
740 V
440 V
660 V
169.
172.
Default
F
5
169

Hide quick links: