YASKAWA CIMR-VU BA0001 Technical Manual page 127

Ac drive-v1000 200 v class, three-phase input: 0.1 to 18.5 kw; 200 v class, single-phase input: 0.1 to 3.7 kw; 400 v class, three-phase input: 0.2 to 18.5 kw
Table of Contents

Advertisement

Setting 1: Reverse Operation Disabled
Drive disregards a Reverse run command or a negative frequency reference.
n
b1-07: LOCAL/REMOTE Run Selection
The drive has the following three separate control sources that can be switched using digital inputs or the LO/RE key on the
digital operator (for details
Reference 1/2 Selection on page 186
248):
• LOCAL - The digital operator is used to set the reference and the Run command.
• REMOTE -Reference 1: The settings of b1-01 and b1-02 determine where the frequency reference and Run command are
input from.
• REMOTE - Reference 2: The settings of b1-15 and b1-16 determine where the frequency reference and Run command are
input from.
When switching from LOCAL to REMOTE, or between Reference 1 and Reference 2, the Run command may already be
present at the location the source was switched to. Parameter b1-07 can be used to determine how the Run command is treated
in this case.
No.
b1-07
Setting 0: Run Command Must Be Cycled
If the Run command is issued differently in the old and new control source (e.g. old - terminals, new - serial communications)
and it is active at the new source when switching takes place, the drive will either not start or it will stop if it was running
before. The Run command has to be cycled to start from the new control source.
Setting 1: Continue Running
If the Run command is active at the new control source, the drive starts or continues running. There is no need to cycle the
Run command.
WARNING! The drive may start unexpectedly if switching control sources when b1-07 = 1. Clear all personnel away from rotating machinery
and electrical connections prior to switching control sources. Failure to comply may cause death or serious injury.
n
b1-08: Run Command Selection while in Programming Mode
As a safety precaution, the drive will not normally respond to a Run input when the digital operator is being used to adjust
parameters in the Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and Auto-Tuning). If required
by the application b1-08 can be used to changed this functionality.
No.
b1-08
Run Command Selection while in Programming Mode
Setting 0: Disabled
A Run command is not accepted while the digital operator is in Programming Mode.
Setting 1: Enabled
A Run command is accepted in any digital operator mode.
Setting 2: Prohibit Programming During Run
It is not possible to enter the Programming Mode as long as the drive output is active.
n
b1-14: Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
No.
b1-14
Setting 0: Standard Phase Order
Setting 1: Switched Phase Order
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Refer to Setting 1: LOCAL/REMOTE Selection on page
and
Refer to o2-01: LO/RE (LOCAL/REMOTE) Key Function Selection on page
Parameter Name
LOCAL/REMOTE Run Selection
Parameter Name
Parameter Name
Phase Order Selection
5.2 b: Application
185,
Refer to Setting 2: External
Setting Range
0 or 1
Setting Range
0 to 2
Setting Range
0 or 1
Default
0
Default
0
5
Default
0
127