• Releasing the acceleration hold input.
• Setting an Up or Down command while no Run command is active.
n
d4-03: Frequency Reference Bias Step (Up/Down 2)
Sets the bias that is added to or subtracted from the frequency reference by the Up/Down 2 function.
No.
d4-03
The operation depends on the set value:
Setting d4-03 = 0.0 Hz
While the Up 2 or Down 2 command is enabled, the bias value is increased or decreased using the accel/decel time determined
by parameter d4-04.
Up 2 command
Setting d4-03 > 0.0 Hz
When an Up 2 or Down 2 command is enabled, the bias is increased or decreased in steps for the value set in d4-03. The
frequency reference changes with the accel/decel times determined by parameter d4-04.
Up 2 command
n
d4-04: Frequency Reference Bias Accel/Decel (Up/Down 2)
Parameter d4-04 determines the accel/decel times that are used for increasing/decreasing the frequency reference or bias when
the Up/Down 2 function is used.
No.
d4-04
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Parameter Name
Frequency Reference Bias Step
Output
frequency
Bias
Figure 5.39 Up/Down 2 Bias when d4-03 = 0.0 Hz
Output
frequency
Bias
Figure 5.40 Up/Down 2 Bias when d4-03 > 0.0 Hz
Parameter Name
Frequency Reference Bias Accel/Decel
5.4 d: Reference Settings
Setting Range
0.00 to 99.99 Hz
Bias value is increased using the
accel/decel times as set in d4-04
Bias value is increased in steps as
defined in d4-03
Drive uses accel/decel times as
set in d4-04
Setting Range
0 or 1
Default
0.00 Hz
5
Default
0
165