4.11 Test Run Checklist
No.
Checklist
Page
Set the minimum and maximum frequency references to the desired values. Make the following adjustments if
the drive does not operate as expected:
Gain adjustment: Set the maximum voltage/current signal and adjust the analog input gain (H3-03 for input A1,
21
H3-11 for input A2) until the frequency reference value reaches the desired value.
Bias adjustment: Set the minimum voltage/current signal and adjust the analog input bias (H3-04 for input A1,
H3-12 for input A2) until the frequency reference value reaches the desired minimum value.
4
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
113