E3: V/F Characteristics For Motor 2 - YASKAWA CIMR-VU BA0001 Technical Manual

Ac drive-v1000 200 v class, three-phase input: 0.1 to 18.5 kw; 200 v class, single-phase input: 0.1 to 3.7 kw; 400 v class, three-phase input: 0.2 to 18.5 kw
Table of Contents

Advertisement

u

E3: V/f Characteristics for Motor 2

These parameters set the V/f pattern used for motor 2.
switching motors.
n
E3-01: Motor 2 Control Mode Selection
Selects the control mode for motor 2. Motor 2 cannot be used in OLV/PM control mode.
No.
E3-01
Setting 0: V/f Control
Setting 2: Open Loop Vector Control
n
E3-04 to E3-13
Parameters E3-04 through E3-13 set up the V/f pattern used for motor 2 like shown in
No.
E3-04
E3-05
E3-06
E3-07
E3-08
E3-09
E3-10
E3-11
E3-12
E3-13
<1> Values shown here are for 200 V class drives. Multiply voltage values by 1.15 for U-spec drives. Double the value when using 400 V class drives.
<2> Default setting is determined by the control mode for motor 2.
Note:
1. The following condition must be true when setting up the V/f pattern: E3-09 ≤ E3-07 ≤ E3-06 ≤ E3-11 ≤ E3-04
2. To make the V/f pattern a straight line set E3-09 = E3-07. In this case the E3-08 setting is disregarded.
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Parameter Name
Motor 2 Control Mode Selection
Parameter Name
Motor 2 Max Output Frequency
Motor 2 Max Voltage
Motor 2 Base Frequency
Motor 2 Mid Output Frequency
Motor 2 Mid Output Frequency Voltage
Motor 2 Minimum Output Frequency
Motor 2 Minimum Output Frequency Voltage
Motor 2 Mid Output Frequency 2
Motor 2 Mid Output Frequency Voltage 2
Motor 2 Base Voltage
Output (V)
E3-05
E3-12
E3-13
E3-08
E3-10
E3-09
Figure 5.43 V/f Pattern for Motor 2
Refer to Setting 16: Motor 2 Selection on page 189
E3-06 E3-11 E3-04
E3-07
Frequency (Hz)
5.5 E: Motor Parameters
for details on
Setting Range
0 or 2
Figure
5.43.
Setting Range
40.0 to 400.0 Hz
<1>
0.0 to 255.0 V
230.0 V
0.0 to 400.0 Hz
0.0 to 400.0 Hz
<1>
0.0 to 255.0 V
0.0 to 400.0 Hz
<1>
0.0 to 255.0 V
0.0 to 400.0 Hz
<1>
0.0 to 255.0 V
<1>
0.0 to 255.0 V
Default
0
Default
60.0 Hz
<1>
60.0 Hz
<2>
<2>
<2>
<2>
0.0 Hz
0.0 Vac
0.0 Vac
5
175