Figure 5.72 Frequency Reference Setting by Analog Input with Inverse Gain and Bias Settings
n
H3-09: Terminal A2 Signal Level Selection
Selects the input signal level for analog input A2. Be sure to also set DIP switch S1 on the terminal board accordingly for a
voltage input or current input.
No.
H3-09
Setting 0: 0 to 10 Vdc with Lower Limit
The input level is 0 to 10 Vdc. Negative input values will be limited to 0. Refer to the explanation of H3-01, Setting 0.
to Setting 0: 0 to 10 Vdc with Limit on page 204
Setting 1: 0 to 10 Vdc without Lower Limit
The input level is 0 to 10 Vdc. Negative input values will be accepted. Refer to the explanation of H3-01, Setting 1.
Setting 1: 0 to 10 Vdc without Limit on page 205
Setting 2: 4 to 20 mA Current Input
The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0 (like setting 0).
Setting 3: 0 to 20 mA Current Input
The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0 (like setting 0).
n
H3-10: Terminal A2 Function Selection
Determines the function assigned to analog input terminal A2.
page 208
for a list of functions and descriptions.
No.
H3-10
n
H3-11/H3-12: Terminal A2 Gain/Bias Setting
Parameter H3-11 sets the level of the selected input value that is equal to 10 Vdc/20 mA input at terminal A2 (Gain).
Parameter H3-12 sets the level of the selected input value that is equal to 0 Vdc/4 mA/0 mA input at terminal A2.
Both can be used to adjust the analog input A2 characteristics. The setting works in the same way as parameters H3-03/04 for
analog input A1.
No.
H3-11
H3-12
n
H3-13: Analog Input Filter Time Constant
Parameter H3-13 sets the time constant for a first order filter that will be applied to both analog inputs A1 and A2.
No.
H3-13
An analog input filter can be used to prevent erratic drive control when a "noisy" analog reference is used. The drive operation
becomes more stable the longer the time programmed, but it becomes less responsive to rapidly changing analog signals.
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Bias = 100 %
Frequency
reference
Gain = 0 %
Name
Terminal A2 Signal Level Selection
Name
Terminal A2 Function Selection
Name
Terminal A2 Gain Setting
Terminal A2 Bias Setting
Name
Analog Input Filter Time Constant
0 V
10 V
Setting Range
Refer to Multi-Function Analog Input Terminal Settings on
Setting Range
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
Setting Range
0.00 to 2.00 s
5.7 H: Terminal Functions
Default
0 to 3
2
Default
0 to 31
0
Default
100.0%
0.0%
Default
0.03 s
Refer
Refer to
5
207