Setting 7: Preset 7 - YASKAWA CIMR-VU BA0001 Technical Manual

Ac drive-v1000 200 v class, three-phase input: 0.1 to 18.5 kw; 200 v class, single-phase input: 0.1 to 3.7 kw; 400 v class, three-phase input: 0.2 to 18.5 kw
Table of Contents

Advertisement

4.6 Application Selection
<1> This is the setting recommended when using Open Loop Vector Control. In V/f Control, set the level as the motor rated slip frequency plus 0.5 Hz.
Not enough motor torque will be created if this value is set too low, and the load may tend to slip. Make sure this value is greater than the minimum
output frequency and greater than the value of L4-02 as shown in the diagram below. If set too high, however, there may be a jolt at start.
<2> Hysteresis for Frequency Detection 2 can be adjusted by changing the Frequency Detection Width (L4-02) between 0.0 and 0.5 Hz. If the load slips
during stop, make changes in steps of 0.1 Hz until the load no longer slips.
The braking sequence should be designed as follows:
• A normally open signal (N.O.) should be used to control the brake so that it is released when terminal P2-PC closes.
• When an Up or Down command is entered, the brake should release.
• When a fault signal is output, the brake should close.
• When changing the speed using an analog signal, make sure that the source of the frequency reference is assigned to the
control circuit terminals (b1-01 = 1).
• A sequence to open and close the holding brake appears in the diagram below.
u

Setting 7: Preset 7

No.
A1-02
Control Method Selection
b1-01
Frequency Reference Selection 1
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
C6-01
Drive Duty Selection
C6-02
Carrier Frequency Selection
d1-01
Frequency Reference 1
d1-02
Frequency Reference 2
d1-03
Frequency Reference 3
H1-05
Multi-Function Digital Input Terminal S5 Function
H1-06
Multi-Function Digital Input Terminal S6 Function
H2-02
Terminals P1 Function Selection
L3-04
Stall Prevention Selection during Deceleration
L8-05
Input Phase Loss Protection Selection
100
L4-01
Output
frequency
Frequency
detection 2
Figure 4.10 Frequency Detection 2
OFF
S1-SC
UP
Input
OFF
Fast/Slow
S6-SC
Output frequency
0
Output
Frequency Detection 2
(H2-03 = 05)
P2-PC
Holding brake
Closed
Figure 4.11 Holding Brake Time Chart
Table 4.17 Preset 7: Parameters and Settings
Parameter Name
L4-02
ON
OFF
ON
ON
b6-02
d1-01 (Enabled when b1-01 = 0)
d1-03
b6-01
b2-01
L4-01
DC Injection braking
OFF
ON
Open
Closed
0: V/f Control
0: Operator
3.0 s
3.0 s
0: Heavy Duty
2: 5 kHz
6.0 Hz
30.0 Hz
60.0 Hz
3: Multi-Step Speed 1
4: Multi-Step Speed 2
37: During frequency output
0: Disabled
1: Enabled
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Time
Time
Default Setting
<1>