Frequency
detection 3 <1>
<1> This is the time chart when L4-07, Speed Agree Detection Selection, is set to 1 (Detection always enabled). The default
setting for L4-07 is 0 (No detection during baseblock). When L4-07 is set to 0, the terminal opens during baseblock.
Refer to L4-03/04: Speed Agreement Detection Level and Detection Width (+/-) on page 227
detection width.
Setting 16: Frequency Detection 4
Output closes whenever the output frequency is equal to or above the detection level set in L4-03. The output opens when the
output frequency falls below L4-03 minus the hysteresis set in L4-04. As the detection level L4-03 is a signed value, the
detection works in the specified direction only.
Status
Open
Output frequency is below L4-03 minus L4-04 or has not exceeded L4-03 yet.
Closed
Output frequency exceeded L4-03.
Frequency
Detection 4
Refer to L4-03/04: Speed Agreement Detection Level and Detection Width (+/-) on page 227
detection width.
Setting 1A: During Reverse
The During Reverse digital output will close whenever the drive is turning the motor in the reverse direction.
Status
Open
Motor is driven in the forward direction or stopped.
Closed
Motor is driven in reverse.
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Output
frequency
OFF
ON
Figure 5.63 Frequency Detection 3 Example with Positive L3-04 Value
Output
frequency
OFF
ON
Figure 5.64 Frequency Detection 4 Example with Positive L3-04 Value
L4-04
L4-03
Description
L4-04
L4-03
Description
5.7 H: Terminal Functions
for details on setting the
for details on setting the
5
201