<5> Maximum MCCB Rating is 15 A or 200% of drive input current rating, whichever is larger. MCCB voltage rating must be 600 Vac or greater.
Additionally, when using MCCBs for protection, the drive must be installed in a ventilated enclosure with minimum volume according the "Minimum
Enclosure Volume" column.
<6> Model 2A0002 requires Mersen (Ferraz) part number A6T6 for compliance.
<7> Models 2A0004 and 4A0004 require Mersen (Ferraz) part number A6T15 for compliance.
<8> Model 4A0005 requires Mersen (Ferraz) part number A6T20 for compliance.
<9> Model 4A0007 requires Mersen (Ferraz) part number A6T25 for compliance.
n
Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The external
power supply shall be a UL-Listed Class 2 power source or equivalent.
Input / Output
Multi-function photocoupler output
Multi-function digital inputs
Multi-function analog inputs
Pulse train input
Pulse train output
n
Drive Short-Circuit Rating
This drive has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current
flow will not rise above 31,000 amps maximum at 240 V for 200 V class drives and 480 V for 400 V class drives.
• The MCCB and breaker protection and fuse ratings shall be equal to or greater than the short-circuit tolerance of the power
supply being used.
• Suitable for use on a circuit capable of delivering not more than 31,000 RMS symmetrical amperes for 240 V in 200 V class
drives (up to 480 V for 400 V class drives) motor overload protection.
u

CSA Standards Compliance

n
CSA for Industrial Control Equipment
The drive is CSA-certified as Industrial Control Equipment Class 3211.
Specifically, the drive is certified to: CAN/CSA C22.2 No. 04-04 and CAN/CSA C22.2 No.14-05.
u

Drive Motor Overload Protection

Set parameter E2-01 (motor rated current) to the appropriate value to enable motor overload protection. The internal motor
overload protection is UL listed and in accordance with the NEC and CEC.
n
E2-01: Motor Rated Current
Setting Range: Model Dependent
Default Setting: Model Dependent
Parameter E2-01 (motor rated current) protects the motor if parameter L1-01 is not set to 0 (default is 1, standard induction
motor protection enabled).
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Table D.11 Control Circuit Terminal Power Supply
Terminal Signal
P1, P2, PC
S1, S2, S3, S4, S5, S6, S7, SC
A1, A2, AC
RP
MP
Figure D.9 CSA Mark
D.3 UL and CSA Standards
Power Supply Specifications
Requires class 2 power supply
Use the internal power supply of the drive. Use class 2 for
external power supply.
Use the internal power supply of the drive. Use class 2 for
external power supply.
Use the internal LVLC power supply of the drive. Use class
2 for external power supply.
Use the internal LVLC power supply of the drive. Use class
2 for external power supply.
D
479

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents