YASKAWA CIMR-VU BA0001 Technical Manual page 208

Ac drive-v1000 200 v class, three-phase input: 0.1 to 18.5 kw; 200 v class, single-phase input: 0.1 to 3.7 kw; 400 v class, three-phase input: 0.2 to 18.5 kw
Table of Contents

Advertisement

5.7 H: Terminal Functions
n
Multi-Function Analog Input Terminal Settings
This section describes the various functions that can be assigned to terminals A1 and A2 by setting H3-02 and H3-10.
Note:
The scaling of all input functions depends on the gain and bias settings for the analog inputs. Set these to appropriate values when selecting
and adjusting analog input functions.
Setting
0
Frequency Bias
1
Frequency Gain
2
Auxiliary Frequency Reference
4
Output Voltage Bias
7
Overtorque/Undertorque Detection Level
B
PID Feedback
C
PID Set Point
E
Motor Temperature (PTC input)
F
Not used/Through Mode
<1> Available in drive software versions PRG: 1016 and later.
Setting 0: Frequency Bias
The input value of an analog input set to this function will be added to the analog frequency reference value. Use this setting
also when only one analog input is used to supply the frequency reference.
By default both analog inputs A1 and A2 are set for this function. Using both A1 and A2 at the same time increases the
frequency reference by the total of both inputs.
Example: If the analog frequency reference by analog input A1 is 50% and a bias of 20% is applied by analog input A2, the
resulting frequency reference will be 70% of the maximum output frequency.
Setting 1: Frequency Gain
The input value of an analog input set to this function will be multiplied with the analog frequency reference value.
Example: If the analog frequency reference from analog input A1 is 80% and a gain of 50% is applied from analog input A2,
the resulting frequency reference will be 40% of the maximum output frequency.
Setting 2: Auxiliary Reference
Sets the auxiliary frequency reference when Multi-Step Speed operation is selected.
page 160
for details.
Setting 4: Voltage Bias
Voltage bias boosts the output voltage of the V/f curve as a percentage of the maximum output voltage (E1-05). Available
only when using V/f Control.
Setting 7: Overtorque/Undertorque Level
Overtorque level sets the overtorque/undertorque detection level using the analog input. This works with Torque Detection
Selection 1 (L6-01) and will take the place of the torque detection level set to L6-02. For general Open Loop Vector Control,
this function is based on 100% of the motor rated torque. For V/f Control and PM Open Loop Vector, this function is based
on 100% of the drive rated current.
Setting B: PID Feedback
An input set for this function supplies the PID feedback value. This setting requires PID operation to be enabled in b5-01.
Refer to PID Feedback Input Methods on page
Setting C: PID Setpoint
An input set for this function supplies the PID setpoint value. The frequency reference selected in parameter b1-01 no longer
becomes the PID se point. This setting requires PID operation to be enabled in b5-01.
Methods on page
137.
Setting E: Motor Temperature
In addition to or in place of the oL1 (motor overload) fault detection, it is possible to use a PTC (Positive Temperature
Coefficient) thermistor for motor insulation protection.
(PTC) on page 215
for detailed explanations.
208
Table 5.29 Multi-Function Input Terminal Settings
Function
Refer to L6: Torque Detection on page 231
137.
Page
Setting
208
10
Forward Torque Limit
208
11
Reverse Torque Limit
208
12
Regenerative Torque Limit
208
15
General Torque Limit
208
16
Differential PID Feedback
208
30
DriveWorksEZ Analog Input 1
208
31
DriveWorksEZ Analog Input 2
208
<1>
Output Voltage Gain
41
209
Refer to Motor Protection Using a Positive Temperature Coefficient
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Function
Refer to Multi-Step Speed Selection on
for details on torque detection.
Refer to PID Setpoint Input
Page
209
209
209
209

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents