B: Application - YASKAWA CIMR-VU BA0001 Technical Manual

Ac drive-v1000 200 v class, three-phase input: 0.1 to 18.5 kw; 200 v class, single-phase input: 0.1 to 3.7 kw; 400 v class, three-phase input: 0.2 to 18.5 kw
Table of Contents

Advertisement

B.2 Parameter Table
No.
Name
A1-06 Application Preset
A1-07
DriveWorksEZ
<2>
Function Selection
A2-01
User Parameters, 1 to 32
to
A2-32
User Parameter
A2-33
Automatic Selection
<1> Parameter can be changed during run.
<2> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330.
<3> Default setting value is dependent on parameter A1-06, Application Selection.
<4> Available in drive software versions PRG: 1020 and later.
<5> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06 ≠ 0.
u

b: Application

Application parameters configure the Run Command Source, DC Injection Braking, Speed Search, Timer functions, PID
control, the Dwell function, Energy Savings and a variety of other application-related settings.
No.
Name
Frequency Reference
b1-01
Selection 1
b1-02
Run Command Selection 1
356
Description
Sets parameters that are commonly used in certain applications to
A2-01 through A2-16 for easier access.
0: General-purpose (A2 parameters are not affected)
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC fan
5: Air compressor
<4>
8: Conveyor 2
Note:
Application Preset settings 6 and 7 are only present in
drive software versions PRG: 1011 and earlier.
0: Disabled
1: Enabled
2: Multi-function input (enabled when H1-oo = 9F)
A2: User Parameters
Use A2 parameters to program the drive.
Parameters that were recently edited are listed here. The user can
also select parameters to appear here for quick access. Parameters
will be stored here for quick access when A1-01 = 1.
0: Parameters A2-01 through A2-32 are reserved for the user to
create a list of User Parameters.
1: Save history of recently viewed parameters. Recently edited
parameters will be saved to A2-17 through A2-32 for quick access.
Description
b1: Operation Mode Selection
Use b1 parameters to configure the operation mode.
Selects the frequency reference input source.
0: Digital operator - Digital preset speed d1-01 to d1-17.
1: Terminals - Analog input terminal A1 or A2.
2: MEMOBUS communications
3: Option PCB
4: Pulse Input (Terminal RP)
Selects the run command input source.
0: Digital operator - RUN and STOP keys on the digital
operator.
1: Digital input terminals
2: MEMOBUS communications
3: Option PCB.
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Control
Mode
Range
Def.
O
V/
P
L
f
M
V
0 to 5; 8
0
A A A
0 to 2
0
A A A
A1-00 to
<3>
A A A
o2-08
<5>
0, 1
A A A
Control
Mode
Range
Def.
O
V/
P
L
f
M
V
0 to 4
1
S
S
S
0 to 3
1
S
S
S
Addr.
Pg.
Hex
127
96
128
119
106 to
120
125
126
120
Addr.
Pg.
Hex
180
121
181
123

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents