H2: Multi-Function Output

n
H2-01 to H2-03: Terminal MA/MB/MC, P1/PC and P2/PC Function Selection
The drive has three multi-function output terminals. Set parameters H2-01 to H2-03 to values between 0 and 192 to assign
functions to these terminals. Default values are listed in the following table.
No.
H2-01
Terminal MA, MB and MC Function Selection (relay)
H2-02
Terminal P1 Function Selection (open-collector)
H2-03
Terminal P2 Function Selection (open-collector)
Note:
Terminals that are not used and terminals using the through-mode should be set to "F".
Setting
0
During Run
1
Zero Speed
2
Speed Agree 1
3
User Set Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
6
Drive Ready
7
DC Bus Undervoltage
8
During Baseblock (N.O.)
9
Frequency Reference Source
A
Run Command Source
B
Torque Detection 1 (N.O.)
C
Frequency Reference Loss
D
Braking Resistor Fault
E
Fault
F
Not used/Through Mode
10
Alarm
11
Reset Command Active
12
Timer Output
13
Speed Agree 2
14
User Set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
17
Torque Detection 1 (N.C.)
18
Torque Detection 2 (N.O.)
19
Torque Detection 2 (N.C.)
1A
During Reverse Operation
<1> Available in drive software versions PRG: 1016 and later.
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Status
Open
Drive is stopped.
Closed
A Run command is input or the drive is during deceleration or during DC injection.
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Parameter Name
Table 5.28 Multi-Function Output Terminal Settings
Function
Page
Setting
195
1B
During Baseblock (N.C.)
196
1C
Motor 2 Selection
196
1E
Restart Enabled
196
1F
Motor Overload Alarm (oL1)
197
20
Drive Overheat Pre alarm (oH)
197
22
Mechanical Weakening
198
<1>
Maintenance Period
2F
198
30
During Torque Limit
198
37
During Frequency Output
198
38
Drive Enable
198
39
Watt Hour Pulse Output
198
3C
LOCAL/REMOTE Status
199
3D
During Speed Search
199
3E
PID Feedback Low
199
3F
PID Feedback High
199
4A
During KEB Operation
199
4B
During Short-Circuit Braking
199
4C
During Fast-stop
199
4D
oH Pre-Alarm Time Limit
199
<1>
Braking Transistor Fault (rr)
4E
200
<1>
Braking Resistor Overheat (rH)
4F
200
90
DriveWorksEZ Digital Output 1
201
91
DriveWorksEZ Digital Output 2
92
DriveWorksEZ Digital Output 3
198
H2 Parameter Functions Reversed Output
100 to 192
Switching of 0 to 92
198
201
Description
5.7 H: Terminal Functions
Setting Range
0 to 192
0 to 192
0: During Run
0 to 192
2: Speed Agree 1
Function
Default
E: Fault
Page
202
202
202
202
202
202
202
202
202
203
203
203
203
203
203
203
203
203
203
203
204
204
5
204
195

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents