Connecting To Connection Cable - Mitsubishi Electric GOT2000 Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000:
Table of Contents

Advertisement

4.2.15 Connecting to connection
cable
Device settings
Write the following set values to devices of each PLC
CPU and initialize each port using a peripheral tool or
DM monitor.
Device name
DM6650
b15 to b8
2)
1) RS-232C port transmission speed setting
02
: 4800bps
H
03
: 9600bps
H
04
: 19200bps
H
DM6651
2) RS-232C port communication frame format
03
(fixed): The settings are:
H
DM6652
*3
DM6653
*1
Only transmission speeds available on the GOT side are
shown.
*2
Set the same transmission speed of the peripheral port as
that of the GOT side.
*3
Set the peripheral port host link station No. according to the
Host Address on the GOT side.
HINT
HINT
HINT
Precautions for changing device values
Before changing the device values, make sure that the
switch settings have been changed as follows:
CPM2A: The communication condition switch to
"individual"
CPM2C: The communication port function switch to
"OFF"
4 - 26
4. CONNECTION TO OMRON PLC
4.2 Serial Connection
Set value
0001
(fixed)
H
b7 to b0
1)
Start bit
: 1 bit
Data length: 7 bits
Stop bit
: 2 bits
Parity
: Even bits
0000 (fixed)
0000 to 0031
4.2.16 Connecting to rack type host
Switch setting on C200H-LK201-V1
Set the switches accordingly.
Front
LK201-V1
RUN
RCV
*1*2
(1)
SW1
(2)
SW3
(1) Setting Machine No. (SW1, SW2)
Set the Machine No. within the range of 00 to 31.
Set the station No. according to the Host Address on
the GOT side.
SW1
(2) Setting transmission speed (SW3)
Set the same transmission speed of the GOT.
SW3
*1
Only transmission speeds available on the GOT side are
shown.
link unit
XM
ERROR
(1)
SW2
(3)
SW4
Rotary
Description
switch
Machine No.
upper digit
SW1
SW2
1
( 10
Machine No.
lower digit
SW2
0
( 10
*1
Setting
4
5
6
Rear
(4)
(5)
Settings
0 to 3
)
0 to 9
)
Settings
4800bps
9600bps
19200bps