Communication Detail Settings - Mitsubishi Electric GOT2000 Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000:
Table of Contents

Advertisement

3.4.2

Communication detail settings

Item
Set this item when change the
transmission speed used for
Transmission
communication with the connected
Speed
equipment.
(Default: 9600bps)
Set this item when change the data
length used for communication with
Data Bit
the connected equipment.
(Default: 8bits)
Specify the stop bit length for
Stop Bit
communications.
(Default: 1bit)
Specify whether or not to perform a
parity check, and how it is performed
Parity
during communication.
(Default: Even)
Set the number of retries to be
performed when a communication
Retry
error occurs.
(Default: 0time)
Set the time period for a
Timeout Time
communication to time out.
(Default: 3sec)
Specify the host address (station No.
of the GOT to which the temperature
*3*4
controller is connected) in the
Host Address
connected network.
(Default: 1)
Set this item to adjust the
transmission timing of the
communication request from the
Delay Time
*1
GOT.
(Default: 1ms)
Select the communication format.
(Default: 1)
*2
format 1: only continuous access
Format
format 2: continuous and random
access
*1
Do not specify "0".
*2
Format is ignored when connecting to DMC50.
*3
Host Address is ignored when connecting to DMC10 or SDC.
*4
Host Address is valid when connecting to DMC50.
Devices to be the target of Host Address setting differ
depending on the system configuration.
<When connecting to the temperature controller via COM
module>
Specify the station No. of the COM module.
<When connecting to the temperature controller directly>
Specify the station No. of the temperature controller.
3 - 50
3. CONNECTION TO AZBIL CONTROL EQUIPMENT
3.4 GOT Side Settings
Description
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 5times
1 to 30sec
1 to 15
0 to 300ms
1/2
POINT
POINT
POINT
Format setting
The compatible format of control equipment differs
depending on model.
Model name
SDC20/21, SDC30/31, SDC40A/40B/40G, CMS,
CMF, CML, MQV, MPC, MVF, PBC201-VN2, RX
DMC10, SDC15, SDC25/26, SDC35/36,
SDC45/46, AUR350C, AUR450C, CMC10B
DMC50, AHC2001
For the continuous access and random access of the
control equipment, refer to the following manual.
User's Manual of the AZBIL control equipment
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
GOT2000 Series User's Manual (Utility)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
Compatible
format
Format 1 only
Format 1 or
Format 2
The format
setting is invalid.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents