1.4.3
Terminating resistors of GOT
The following shows the terminating resistor specifications on the GOT side.
When setting the terminating resistor in each connection type, refer to the following.
RS-422/485 communication unit
Set the terminating resistor using the terminating
resistor setting switch.
Switch No.
Terminating
*1
resistor
1
100 OHM
ON
Disable
OFF
*1
The default setting is "Disable".
• For RS422/485 communication unit
Terminating resistor setting switch
Rear view of RS-422/485 communication unit.
1 - 22
1. PREPARATORY PROCEDURES FOR MONITORING
1.4 Connection Cables for the Respective Connection
2
ON
OFF
SW1
ON
GT27
Set the terminating resistor using the terminating
resistor setting switch.
Switch No.
Terminating
*1
resistor
1
100 OHM
ON
Disable
OFF
*1
The default setting is "Disable".
• For GT2710-V
Terminating resistor setting switch
(inside the cover)
• For GT2310-V
Terminating resistor setting switch
(inside the cover)
2
ON
OFF