3.5.14 Connecting to AUR350C,
AUR450C
Communication settings
Make the communication settings by operating the
Smart Loader Package (SLP-A35, SLP-A45) of the
control equipment.
Item
*1
9600bps, 19200bps
Transmission speed
8-bit data length, Even parity, Stop bit 1
Communication condition
*1
selection
8-bit data length, Non parity, Stop bit 2
*2*3
0 to F
Station address
*1
Adjust the settings with GOT settings.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.
Station address setting
Set the station address switch.
(1) For AUR350C
(2) For AUR450C
S
Set value
Station No. setting switch
Station No. setting switch
3. CONNECTION TO AZBIL CONTROL EQUIPMENT
3.5.15 Connecting to RX
Communication settings
Make the communication settings by operating the
Smart Loader Package (SLP-RX) of the control
equipment.
Item
*1
9600bps, 19200bps ,38400bps
Transmission speed
Even parity stop 1
(8-bit data length, Even parity, Stop bit 1)
Even parity stop 2
(8-bit data length, Even parity, Stop bit 2)
Communication condition
*1
selection
Odd parity stop 1
(8-bit data length, Odd parity, Stop bit 1)
Odd parity stop 2
(8-bit data length, Odd parity, Stop bit 2)
*2*3
1 to 32
Station address
*1
Adjust the settings with GOT settings.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.
3.5.16 Connecting to CMC10B
Communication settings
Make the communication settings by operating the
Smart Loader Package (SLP-CM1) of the control
equipment.
Item
*1
9600bps, 19200bps
Transmission speed
0:8-bit data length, Even parity, Stop bit 1
*1
Communication format
1:8-bit data length, Non parity, Stop bit 2
*2*3
0 to 99
Station address
*1
Adjust the settings with GOT settings.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.
Station address setting
Set the station address switch.
Station No. setting switch
3.5 Control Equipment Side Setting
3
Set value
Set value
3 - 55