4.4.2
OMRON PLC (OMRON
SYSMAC CS/CJ)
Device name
Setting range
I/O relay/internal
..000000 to ..614315
auxiliary relay (...)
Data link relay (LR)
LR00000 to LR19915
Auxiliary memory
AR000000 to AR147115
relay (AR)
AR1000000 to AR1153515
Holding relay (HR)
HR00000 to HR51115
Internal auxiliary
relay/Work relay
WR00000 to WR51115
(WR)
Timer contact (TIM)
TIM0000 to TIM4095
Counter contact
CNT0000 to CNT4095
(CNT)
Specified bit of the following
word devices
(except data link relay,
*1*4
Word device bit
auxiliary memory relay,
holding relay
and internal auxiliary relay.)
I/O relay/internal
..0000 to ..6143
auxiliary relay (...)
Data link relay (LR)
LR000 to LR199
Auxiliary memory
AR0000 to AR1471
relay (AR)
AR10000 to AR11535
Holding relay (HR)
HR000 to HR511
Internal auxiliary
relay/Work relay
WR000 to WR511
(WR)
Data memory (DM)
DM00000 to DM32767
Timer (current value)
TIM0000 to TIM4095
*3
(TIM)
Counter (current
CNT0000 to CNT4095
*3
value) (CNT)
Extension data
memory (EM current
EM00000 to EM32767
*2
bank)
Extension data
E000000 to E032767
memory (E0 to EC:
*2
E1800000 to E1832767
13banks)
*1
When executing the touch switch function set during the bit
specification of the word device, do not write any data to the
word device through the sequence program.
*2
Writing or reading the extension data memory using multiple
banks is not allowed.
*3
Timer (current value) and counter (current value) are valid
within the range of 0 to 9999.
(This applies to the 16 bit/32 bit device data.)
*4
This is not supported by GT10.
Device No.
representation
Decimal +
Hexadecimal
Decimal
-
Decimal
:
4. CONNECTION TO OMRON PLC
4.4 Device Range that Can Be Set
4
4 - 39

Hide quick links: