3.5.11

Connecting to MPC

Communication settings
Make the communication settings by operating the key
of the control equipment.
Item
*1
9600bps, 19200bps, 38400bps
Transmission speed
0: 8-bit data length, Even parity, Stop bit 1
Communication condition
*1
selection
1: 8-bit data length, Non parity, Stop bit 2
*2*3
0 to 127
Station address
*1
Adjust the settings with GOT settings.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.
3.5.12 Connecting to PBC201-VN2
Communication settings
Make the communication settings by operating the key
of the control equipment.
Item
Communication protocol
CPL
*1
9600bps, 19200bps, 38400bps, 115200bps
Transmission speed
0:Even parity, Stop bit 1
Communication condition
*1
1:Odd parity, Stop bit 1
selection
(Fixed 8-bit data length)
2:Non parity, Stop bit 2
*2*3
0 to 126
Station address
*1
Adjust the settings with GOT settings.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.
3.5.13 Connecting to MVF
Communication settings
Make the communication settings by operating the
switch of the control equipment.
Item
*1
9600bps, 19200bps
Transmission speed
8-bit data length, Even parity, Stop bit 1
Communication condition
*1
selection
8-bit data length, Non parity, Stop bit 2
*2*3
0 to F
Station address
*1
Adjust the settings with GOT settings.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.
3 - 54
3. CONNECTION TO AZBIL CONTROL EQUIPMENT
3.5 Control Equipment Side Setting
Set value
Set value
Set value
Settings by switch
Display section
(1) Transmission speed settings
Set the communication condition switch.
Switch No.
Transmission
speed (bps)
1
2
9600
ON
ON
19200
ON
OFF
(2) Communication condition selection
Set the communication condition switch.
Communication condition
8-bit data length, Even parity, Stop bit 1
8-bit data length, Non parity, Stop bit 2
(3) Station address setting
Set the station address switch.
Station No. setting switch
Communication condition
switch
Station No. setting switch
3
OFF
OFF
Switch No.
4
OFF
ON