6.3.2

GOT side settings

Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: KEYENCE
• Controller Type: KEYENCE KV-700/1000/3000/
5000
• I/F: Interface to be used
• Driver: Ethernet(KEYENCE), Gateway
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
6.3.2 ■ Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
6 - 16
6. CONNECTION TO KEYENCE PLC
6.3 Ethernet Connection
Click!
[Controller Setting] from the
Communication detail settings
Make the settings according to the usage environment.
3.
4.
Item
GOT Net No.
GOTStation
GOT Ethernet
Setting
GOT
Communication
Port No.
Retry
Startup Time
Timeout Time
Delay Time
Description
Set the network No. of the GOT.
(Default: 1)
Set the station No. of the GOT.
(Default: 1)
Set the GOT IP address, subnet
mask, default gateway, peripheral
S/W communication port No.,
transparent port No.
Set the GOT port No. for the
connection with the Ethernet
module.
(Default: 5025)
Set the number of retries to be
performed when a communication
timeout occurs.
When receiving no response after
retries, the communication times
out.
(Default: 3times)
Specify the time period from the
GOT startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
load of the network/destination
PLC.
(Default: 0ms)
Range
1 to 239
1 to 254
GOT
Ethernet setting
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013, and
49153)
0 to 5times
3 to 255sec
1 to 90sec
0 to 10000
( 10ms)