Monitoring The Device Functions Via The Signal Contact - Hirschmann RS20 User Manual

Hide thumbs Also See for RS20:
Table of Contents

Advertisement

Operation Diagnosis
9.3.3
Monitoring the Device Functions via the
Signal Contact
Configuring the operation monitoring
 Select the Diagnostics:Signal Contact dialog.
 Select "Monitoring correct operation" in the "Mode signal contact"
frame to use the contact for operation monitoring.
 In the "Monitoring correct operation" frame, you select the events
you want to monitor.
 To monitor the temperature, you set the temperature thresholds in
the Basics:System dialog at the end of the system data.
enable
configure
signal-contact 1 monitor all Includes all the possible events in the operation
signal-contact 1 trap enable Enables a trap to be sent if the status of the
Displaying the signal contact's status
The device gives you 3 additional options for displaying the status of the
signal contact:
LED display on device,
display in the Web-based interface,
query in the Command Line Interface.
168
9.3 Out-of-band Signaling
Switch to the privileged EXEC mode.
Switch to the Configuration mode.
monitoring.
operation monitoring changes.
UM BasicConfig L2E
Release 8.0 05/2013

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rs30Rs40Ms20Ms30

Table of Contents