4.35 Display function (Pr. 867)

4.35.1 DA1 output response level adjustment (Pr. 867
You can adjust the response level of the output voltage of the output signal DA1.
Parameter
Name
867
DA1 output filter

4.36 Terminal function assignment (Pr. 868)

4.36.1 No. 1 terminal function assignment (Pr. 868
The terminal 1 can be multi-functioned.
Parameter
Name
No. 1 terminal function
868
assignment
<No1. terminal function according to control>
Terminal 1
Pr. 868
Function under
Setting
Speed Control
Speed setting
0
auxiliary
(factory
*
setting)
Magnetic flux
1
command
Regenerative
2
torque restriction
5
No function
9999
No function
* The function is changed to main speed according to the Pr.73 setting with which override, polarity reversible
function, etc. can be selected. (Refer to page 125.)
REMARKS
Refer to page 202 for bias/gain settings.
Factory Setting
Setting Range
0.05s
Factory Setting
0
Terminal 1 Function
Function under
under Torque Control
Position Control
Speed restriction
No function
auxiliary
Magnetic flux
Magnetic flux command
command
Regenerative
No function
torque restriction
Forward/reverse rotation
speed restriction
(analog polarity
No function
switchover speed
restriction)
No function
No function
195
Display function (Pr. 867)
with
without
Encoder
Encoder
Speed
Remarks
0 to 5s
Extended mode
with
without
Encoder
Encoder
Speed
Setting Range
Remarks
0, 1, 2, 5, 9999
Extended mode
Terminal 1
Bias/Gain Setting
Pr. 902 "speed setting
No. 2 bias"
Pr. 903 "speed setting
No. 2 gain"
Pr. 919 "No. 1 terminal
bias (torque/magnetic
flux)"
Pr. 920 "No. 1 terminal
gain (torqe/magnetic flux)"
Pr. 919 "No. 1 terminal
bias (torque/magnetic
flux)"
Pr. 920 "No. 1 terminal
gain (torqe/magnetic flux)"
Pr. 917 "No. 1 terminal
bias (speed)"
Pr. 918 "No1. terminal gain
(speed)"
No function
with
without
Condi-
tional PLC
SSC
Encoder
Encoder
)
Position
Torque
with
without
Condi-
tional PLC
SSC
Encoder
Encoder
)
Torque
Position
Remarks
Setting can be
made when
Pr. 810 = 1.
No function
4