Parameter Write Disable Selection (Pr. 77) - Mitsubishi Electric FR-V560 Instruction Manual

Vector inverter
Table of Contents

Advertisement

Operation selection function 2 (Pr. 65 to Pr. 79)
(2) Restarting method when stop was made by inputting
1) After the motor has decelerated to
a stop, turn off the STF or STR
signal.
2) Press
EXT
.
..... (Recovery from
3) Turn on the STF or STR signal.
Alternatively, you can make a restart by making a power-on reset or resetting the inverter using the reset terminal of
the inverter.
REMARKS
• When you provide a reset input (RES) during operation, the inverter that is being reset shuts off the output and resets the
data of the electronic thermal relay function, and the motor coasts.
• To make a restart, confirm that the PU is connected and then reset the inverter.
• The Pr. 75 value can be set any time. This value does not return to the initial value even if parameter (all) clear is executed.
• When the motor is stopped from the PU, PS is displayed. An alarm output is not provided.
• Pr. 250 is made invalid.
Do not reset the inverter with the start signal input.
Doing so will start the inverter immediately after it has recovered from the error, causing hazard.
4.11.6 Parameter write disable selection (Pr. 77
You can select between enable and disable for parameter write. This function is used to prevent parameter
values from being rewritten by misoperation.
Parameter
77
Parameter write disable selection
<Setting>
Pr. 77 Setting
0
Write is enabled only during a stop in the PU operation mode.*
1
Parameter write is disabled.
Write is enabled even during operation. Write is enabled independently of the operation
2
mode.
CAUTION
• * The shaded parameters in the parameter list (refer to page 78) always allow setting.
• Even when "2" is set in Pr. 77, the following parameters do not allow writing during operation.
Pr. 60, Pr. 71, Pr. 72, Pr. 79, Pr. 80 to Pr. 84, Pr. 90 to Pr. 96, Pr. 180 to Pr. 183, Pr. 187, Pr. 190 to Pr. 192,
Pr. 195, Pr. 450, Pr. 451, Pr. 453, Pr. 454, Pr. 800, Pr. 819, Pr. 851, Pr. 852, Pr. 859 and Pr. 868
Stop operation when changing the values of the above parameters.
• By setting "1" in Pr. 77, the following clear operations can be inhibited:
• Parameter clear
• Parameter all clear
Even when "1" is set in Pr. 77, write is allowed for Pr. 22, Pr. 75, Pr. 77 and Pr. 79.
Speed
Operation panel
)
STF
ON
(STR) OFF
CAUTION
Factory
Name
Setting
STOP
RESET
EXT
STOP
RESET
Example of stop and restart during external operation
with
without
Encoder
Encoder
Speed
Setting Range
0
0, 1, 2
Function
128
from PU
Time
with
without
Condi-
tional PLC
SSC
Encoder
Encoder
Torque
Position
Remarks
Simple mode
)