Offline auto tuning (Pr. 80 to Pr. 96)
3. In the parameter setting mode, read the following parameters and set desired values.
Parameter Number
Motor excitation current
82 (455)
(no load current)
90 (458)
Motor constant R1
91 (459)
Motor constant R2
92 (460)
Motor constant L1
93 (461)
Motor constant L2
94 (462)
Motor constant x
859 (860)
Torque current
4. Return the Pr. 77 setting to the original value.
5. Refer to the following table and set Pr. 83 and Pr. 84 (Pr. 456 to Pr. 457).
Parameter Number
83 (456)
Rated motor voltage
84 (457)
Rated motor frequency
CAUTION
Set "9999" in Pr. 90 to Pr. 94 (Pr. 458 to Pr. 462) to use the standard motor constants (including those for
the constant-torque motor).

4.12.6 Direct input + offline auto tuning

Perform offline auto tuning after directly inputting the motor constants.
1. Set Pr. 71 (Pr. 450).
Pr. 71 Setting
7
Star connection direct input + offline auto tuning
8
Delta connection direct input + offline auto tuning
17
Star connection direct input + offline auto tuning
18
Delta connection direct input + offline auto tuning
2. Set the motor constants (Refer to page 137).
3. Set Pr. 96 (Pr. 463) to perform offline auto tuning (Refer to page 133).
Name
Setting Range Setting Increments Factory Setting
0 to 500A
0 to 50Ω, 9999
0 to 50Ω, 9999
0 to 1000mH,
9999
0 to 1000mH,
9999
0 to 100%,
9999
0 to 500A
Name
Setting Range
0 to 1000V
20 to 200Hz
0.01A
0.001Ω
0.001Ω
0.1mH
0.1mH
0.1%
0.01A
Setting Increments
0.1V
0.01Hz
Description
138
9999
9999
9999
9999
9999
9999
9999
Factory Setting
575V
60Hz
General-purpose motor
Constant-torque motor