Operation Panel
E.LF
Indication
Name
Output phase failure protection
This function stops the inverter output if one of the three phases (U, V, W) on the inverter's output
Description
side (load side) opens.
• Check the wiring (Check the motor for a fault.)
Check point
• Check that the capacity of the motor used is not smaller than that of the inverter.
• Wire the cables properly.
Corrective action
• Check the Pr. 251 "output phase failure protection selection" setting.
Operation Panel
E.CPU
Indication
Name
CPU error
Description
Stops the inverter output if the communication error of the built-in CPU occurs.
Check point
Corrective action
Please contact your sales representative.
E. 6
Operation Panel
Indication
E. 7
Name
CPU error
If the arithmetic operation of the peripheral circuit of the built-in CPU does not end within the
Description
predetermined period or if an error exists in the receive data of the built-in CPU, the inverter self-
determines it as an alarm and stops the output.
Check point
Check for excess electrical noises around the inverter.
• Connect devices securely.
• If there are any devices generating excessive electrical noise around the inverter, take measures
Corrective action
against noise.
• Please contact your sales representative.
Operation Panel
E.P24
Indication
Name
24VDC power output short circuit
When the 24VDC power output from the PC terminal is shorted, this function shuts off the power
output.
Description
At this time, all external contact inputs switch off. The inverter cannot be reset by entering the RES
signal. To reset it, use the operation panel or switch power off, then on again.
When the 24VDC power for encoder is shorted, this function shuts off the power output.
• Check for a short circuit in the PC terminal output.
Check point
• Check for wrong wiring.
• Check for a loose connector. Check that the cables are short-circuited.
• Remedy the short circuit portion.
Corrective action
• Connect the cables securely. Change the cables.
Operation Panel
E.P12
Indication
Name
12VDC power output short circuit
Description
When the 12VDC power for encoder is shorted, this function shuts off the power output.
• Check for wrong wiring.
Check point
• Check for a loose connector. Check for a break in the cable.
Corrective action
Connect the cables securely. Change the cables.
Operation Panel
E.CTE
Indication
Name
Operation panel power supply short circuit
When the operation panel power supply (P5S of the PU connector) is shorted, this function shuts
off the power output. At this time, the operation panel (parameter unit) cannot be used and RS-485
Description
communication from the PU connector cannot be made. To reset, enter the RES signal or switch
power off, then on again.
When the 5VDC power for encoder is shorted, this function shuts off the power output.
• Check for a short circuit in the PU connector cable. Check for a loose connector.
Check point
• Check that cables are short-circuited.
• Check for wrong wiring.
FR-PU04V
ELF
FR-PU04V
CPU Fault
Fault 6
FR-PU04V
Fault 7
FR-PU04V
E.P24
FR-PU04V
E.P12
FR-PU04V
213