Operation selection functions 4 (Pr. 800 to Pr. 809)
(3) When Pr. 807 = 2
Using the analog input of the terminal 1, set the forward rotation and reverse rotation speed restriction levels.
At this time, the speed restriction made on the analog input is as shown below.
1) When terminal 1 input is -10 to 0V
Reverse rotation speed restriction
Speed
Forward
rotation
Output
torque
Pr. 1 "maximum speed"
No. 1 terminal input
is -10 to 0V
Start signal
Related parameters
• Selection of No. 1 terminal function ⇒ Pr. 868 "No. 1 terminal function assignment" (Refer to page 195.)
• Speed restriction during acceleration/deceleration ⇒ Pr. 7 "acceleration time", Pr. 8 "deceleration time" (Refer to page 91.)
• DC injection brake operation level ⇒ Pr. 10 "DC injection brake operation speed" (Refer to page 95.)
• Speed restriction level maximum setting ⇒ Pr. 1 "maximum speed" (Refer to page 89.)
CAUTION
When speed
speed restriction, torque control is switched to speed control.
Pr. 810, Pr. 812 to Pr. 817
Pr. 1 "maximum speed"
Torque controllable range
150% torque
No. 1 terminal input
Reverse
rotation
Speed
Pr.7
Refer to Pr. 22 (page 100)
2) When terminal 1 input is 0V to 10V
Forward rotation speed restriction
Actual speed
Speed restriction operation
Pr.8
186
Speed
Forward
rotation
No. 1 terminal input
Output torque
Pr. 1 "maximum speed"
Reverse
rotation
Torque controllable range