<Setting>
There are three methods to adjust the speed setting voltage bias and gain.
1) Method to adjust any point by application of voltage to across terminals 2-5
2) Method to adjust any point without application of voltage to across terminals 2-5
3) Method that does not adjust the bias voltage
Pr. 903 "speed setting No. 2 gain"
(You can also adjust Pr. 902 to Pr. 905 and Pr. 917 to Pr. 920 in the similar manner.)
<Adjustment procedure> Using the speed setting signal from the operation panel (FR-DU04
(1) Power on (Monitoring mode)
FR-DU04
-1
CONTROL PANEL
Hz/r
A
V
MON
EXT
PU
REV
FWD
REMARKS
ON of the LED is indicated by
2. Set "1" (PU operation mode) in Pr. 79 "operation mode selection".
Example: To change the external operation mode (Pr. 79 = 2) to the PU operation mode (Pr. 79 = 1)
As in the procedure in 1), press
Parameter setting mode
FR-DU04
-1
CONTROL PANEL
Hz/r
SET
A
V
MON
EXT
PU
REV
FWD
Current setting
SET
(3) Read Pr. 903 to display the currently set gain speed. (You can also adjust Pr. 902, Pr. 904 and Pr. 905 in a similar manner.)
Parameter setting mode
As in the procedure in (2)-1), press
choose the "parameter setting mode".
FR-DU04
-1
CONTROL PANEL
Hz/r
MON
EXT
PU
REV
FWD
Currently set gain speed
FR-DU04
-1
CONTROL PANEL
Hz/r
MON
EXT
PU
REV
FWD
, and OFF by
.
to choose the "parameter setting mode".
MODE
Most significant
Middle digit flickering
digit flickering
SET
Press for
1.5 s
Setting change
SET
Flicker
to
MODE
Most significant
digit flickering
SET
A
V
0 to 9
A
V
Calibration functions (Pr. 900 to Pr. 920)
(2) Choose the PU operation mode.
MODE
1. Press
to make sure that the inverter is in the PU
operation mode. (LED of PU is lit.) (For monitoring displays,
refer to the Instruction Manual (basic).)
Operation mode (PU operation mode)
FR-DU04
-1
CONTROL PANEL
MON
EXT
REV
Least significant
digit flickering
×7 times
SET
0 to 9
Setting write
If
Check that the forward rotation (STF)
or reverse rotation (STR) signal connected
to the control terminal is not on. If on, turn it off.
"1" (PU operation mode) has been set in Pr. 79.
If
1.5s when writing the value.
Press
more time.
Middle digit flickering
×9 times
SET
203
-1
) to make speed setting
Hz/r
A
V
PU
FWD
×9 times
0 to 9
appears
appears, you did not press
for
SET
once, press
, and make setting one
SET
Least significant
digit flickering
SET
×3 times
SET
0 to 9
4