Offline auto tuning (Pr. 80 to Pr. 96)
(1) Parameter setting
• Select Pr. 851 "number of encoder pulses" and Pr. 852 "encoder rotation direction" (Refer to page 10.)
(It is not necessary to select when using the motor without encoder.)
• Select Pr. 80 (Pr. 453) "motor capacity" and Pr. 81 (Pr. 454) "number of motor poles".
• Refer to the parameter details to set the parameters below.
1) Set "1" or "101" in Pr. 96 (Pr. 463)
•When the setting is "1" . . . . .tuning performed without motor running
•When the setting is "101" . . .tuning performed with motor running
2) Set Pr. 9 (Pr. 452) "electronic thermal O/L relay".
When using the external thermal, change the Pr. 9 (Pr. 452) setting back to "0" after offline auto tuning. The
electronic thermal function is made invalid. Set "0" in Pr. 876 if the external thermal relay is not used.
3) Set the rated motor voltage (V) in Pr. 83 (Pr. 456).
4) Set the rated motor frequency (Hz) in Pr. 84 (Pr. 457).
5) Select the motor in Pr. 71 (Pr. 450).
Example
•Standard motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pr. 71 (Pr. 450) = "3"
•Constant torque motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pr. 71 (Pr. 450) = "13"
•SF-JR 4 poles (1.5kW (2HP) or less) . . . . . . . . . . . . . . . . . . . . . . . . . Pr. 71 (Pr. 450) = "23"
•Vector control dedicated motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pr. 71 (Pr. 450) = "33"
CAUTION
For the setting value, set the motor rating plate value..
(2) Tuning command
After setting the above parameters, press
(For external operation, turn on the run command (STF, STR).)
REMARKS
• To force tuning to end, use the MRS or RES signal or press
• Excitation noise is produced during tuning.
• When executing offline auto tuning, input the run command after switching on the main circuit power (R, S, T) of the inverter.
(3)
Monitoring during execution
When the parameter unit (FR-PU04V) is used, the Pr. 96 (Pr. 463) value is displayed during tuning on the main
monitor as shown on the next page. When the operation panel (FR-DU04-
is only displayed.
When Pr.96=1
• Parameter unit (FR-PU04V) main monitor
1. Setting
Display
• Operation panel (FR-DU04-
1. Setting
Displayed
value
REMARKS
• Offline auto tuning time (factory setting)
1: No-rotation mode: Approx. 25s
2: Rotation mode: Approx. 40s
(Offline auto tuning time varies with the acceleration and deceleration time settings as indicated below.
Offline auto tuning time = acceleration time + deceleration time + approx. 30s)
or
FWD
REV
2. Tuning in progress
TUNE
1
STOP
PU
STF
FWD
) display
1
2. Tuning in progress
.
STOP
. (The start signal may also be turned off to end.)
RESET
1
) is used, the same value as on the PU
3. Completion
TUNE
3
2
COMPLETION
STF
STOP
PU
PU
3. Completion
134
4. Error-activated end
(for inverter trip)
TUNE
9
ERROR
STF
STOP
PU
4. Error-activated end
(for inverter trip)