4.2.22 Monitor display / FM, AM terminal function selection
(Pr. 52 to Pr. 54, Pr. 158)
Pr. 52 "DU/PU main display data selection"
Pr. 53 "PU level display data selection"
Pr. 54 "FM terminal function selection"
Pr. 158 "AM terminal function selection"
You can select the signals shown on the operation panel (FR-DU04)/parameter unit (FR-PU04) main display
screen and on the parameter unit (FR-PU04) level meter and signals output to the FM and AM terminals.
# There are two different signal outputs: FM pulse train output terminal and AM analog output terminal. Select
the signals using Pr. 54 and Pr. 158.
Parameter Number
52
53
54
158
<Setting>
Set Pr. 52 to Pr. 54 and Pr. 158 in accordance with the following table:
Signal Type
No display
Output frequency
Output current
Output voltage
Alarm display
Frequency setting
Running speed
Converter output voltage
Regenerative brake duty
Electronic overcurrent
protection load factor
Output current peak value
Converter output voltage
peak value
Input power
Output power
Input terminal status
Output terminal status
Load meter **
Cumulative operation time
Reference voltage output
Actual operation time
Motor load factor
Cumulative power
Factory Setting
0
1
1
1
Pr.52
Unit
PU
DU
main
LED
monitor

×
Hz
0/100
0/100
A
0/100
0/100
V
0/100
0/100

0/100
0/100
Hz
5
r/min
6
V
8
×
%
%
10
A
11
V
12
kW
13
kW
14

×

×
%
17
17
h
20
20

×
h
23
23
%
24
24
kWh
25
25
Pr. 37 "speed display"
Pr. 55 "frequency monitoring reference"
Pr. 56 "current monitoring reference"
Pr. 170 "watt-hour meter clear"
Pr. 171 "actual operation hour meter
Pr. 900 "FM terminal calibration"
Pr. 901 "AM terminal calibration"
0, 5, 6, 8, 10 to 14, 17, 20, 23, 24, 25, 100
0 to 3, 5, 6, 8, 10 to 14, 17
1 to 3, 5, 6, 8, 10 to 14, 17, 21
1 to 3, 5, 6, 8, 10 to 14, 17, 21
Parameter Setting
Pr.53
Pr.54
PU level
FM
meter
terminal
×
×
0
1
1
2
2
3
3
×
×
*
5
5
*
6
6
*
8
8
×
×
*
*
10
10
*
11
11
*
12
12
*
13
13
*
14
14
×
×
*
×
×
*
17
17
×
×
×
×
21
×
×
×
×
×
×
88
PARAMETERS
Related parameters
clear"
Setting Range
Pr.158
Full-Scale Value of
FM, AM, Level Meter
AM
terminal
×
1
2
3
400V or 800V
×
5
Pr. 55 value converted into Pr. 37
6
value
8
400V or 800V
×
10
Protection operation level
11
12
400V or 800V
Rated power of inverter rating × 2
13
Rated power of inverter rating × 2
14
×
×
17
×
1440Hz is output to FM terminal.
21
Full-scale voltage is output to AM
terminal.
×
×
Rated inverter current × 2
×

Pr. 55
Pr. 56

Pr. 55

Pr. 56


Pr. 56


