Mitsubishi Electric FR-V560 Instruction Manual page 108

Vector inverter
Table of Contents

Advertisement

<Wiring example> For sink logic
REMARKS
• Set the MRS signal using the input terminal function selection (Pr. 180 to Pr. 183, Pr. 187).
• The setting cannot be changed during operation.
Refer to page 218 for inverter reset.
CAUTION
• When the operation mode is the NET mode and Pr. 338 = 0, the MRS signal is used as both the external
terminal and communication-based signals, and the output stops when either signal turns on. At the
Pr. 17 setting of 2, the output stops when either signal turns off. (Oppositely, at the Pr. 17 setting of 2,
both the external terminal and communication-based signals should turn on to make a start.)
Related parameters
• Starting speed setting ⇒ Pr. 13 "starting speed" (Refer to page 97.)
• MRS signal terminal assignment ⇒ Pr. 180 to Pr. 183, Pr. 187 (input terminal function selection) (Refer to page 163.)
Pr. 19
Refer to Pr. 3 (page 90)
Pr. 20, Pr. 21
Refer to Pr. 7, Pr. 8 (page 91)
Operation selection functions 1 (Pr. 17 to Pr. 37)
Setting 0
(factory setting)
Setting 2
Inverter
Output
Output
stop
stop
MRS
SD
99
Inverter
MRS
SD
4