Others
1.9.7

Using the PU connector for computer link

(1) When connecting the operation panel or parameter unit using a connection cable
Refer to the Instruction Manual (basic).
(2) For RS-485 communication
The PU connector can be used to perform communication operation from a personal computer etc.
By connecting the PU connector to computers such as a personal computer and Factory Automation computer with
a communication cable, you can monitor the inverter operation and read and write parameters using a user
program.
<PU connector pin-outs>
Viewed from the inverter (receptacle side) front
CAUTION
1. Do not connect the PU connector to the computer's LAN board, FAX modem socket or telephone
modular connector. Otherwise, the product may be damaged due to electrical specification
differences.
2. Pins No. 2 and 8 (P5S) provide power to the operation panel or parameter unit.
Do not use these pins for RS-485 communication.
<System configuration example>
(1) Connection of a computer to the inverter (one-to-one connection)
Computer
RS-485
Interfase
terminal
Computer - inverter connection cable
For a connection cable between the computer having RS-232C and the inverter (RS-232C⇔RS-485
converter), refer to the table below.
Examples of commercially available products (as of July, '02)
Type
FA-T-RS40
* You can not connect multiple inverters with a converter cable (a computer and an inverter are one-to-one
connection). As the RS-232C cable and the RS-485 cable (10BASE-T+RJ-45 connector) are provided with a
product, no need to prepare a cable and a connector separately. Contact a maker for details of the product.
REMARKS
When fabricating the cable on the user side, see below.
Examples of commercially available products (as of July, '02)
Product
1)
10BASE-T cable
2)
RJ-45 connector
8)
1)
Station No.0
Inverter
RS-232C
RS-485
connector
cable
RJ-45
connector 2)
10BASE-T cable 1)
Mitsubishi Electric Engineering Co., Ltd
*
Type
SGLPEV-T 0.5mm × 4P
* Do not use No. 2 and No. 8 pin (P5S).
5-554720-3
1) SG
5) SDA
2) P5S
6) RDB
3) RDA
7) SG
4) SDB
8) P5S
Station No.0
Computer
RS-232C
connector
Maximum
15m (49.21feet)
RS-232C
RS-485
converter
10BASE-T cable 1)
Maker
Maker
Mitsubishi Cable Industries, Ltd.
Tyco Electronics Corporation
26
Inverter
RS-485
connector
RJ-45 connector 2)