Advertisement

Terminal assignment functions (Pr. 180 to Pr. 195)
<Setting>
Refer to the following table and set the parameters.
Signal
Setting
Name
Pr. 59 = 0
0
RL
Pr. 59 = 1, 2 *
Pr. 59 = 0
1
RM
Pr. 59 = 1, 2, 3 *
Pr. 59 = 0
2
RH
Pr. 59 = 1, 2, 3*
3
RT
Second function selection
5
JOG
Jog operation selection
15-speed selection (combination with three speeds RL,
8
REX
RM, RH)
9
X9
Third function
10
Maker setting value. Do not make setting.
11
Maker setting value. Do not make setting.
12
X12
PU operation external interlock signal
14
X14
PID control enable terminal
15
BRI
Brake sequence opening completion signal
16
X16
PU/external operation switchover
20
X20
S-pattern acceleration/deceleration C switchover
22
X22
Orientation command (Caution 4)
23
LX
Pre-excitation/servo on (Caution 5)
24
MRS
Output stop
25
STOP
Start self-holding selection
26
MC
Control mode changing
27
TL
Torque restriction selection
28
X28
Start time tuning
42
X42
Torque bias selection 1
43
X43
Torque bias selection 2
44
X44
P control selection (P/PI control switchover)
9999
STR
Reverse rotation start
When Pr. 59 = "1, 2, or 3", the functions of the RL, RM, RH and RT signals change as listed above.
*
CAUTION
1. One signal can be assigned to two or more terminals. In this case, turning on any one of the terminals
make the signal valid.
2. The speed command priorities are higher in order of jog, multi-speed setting (RH, RM, RL, REX) and
PID (X14).
3. Use common terminals to assign multi-speeds (7 speeds) and remote setting. They cannot be set
individually.
4. The FR-A5AX (12-bit digital input) is needed to externally input a stop position under orientation control.
5. Made valid under vector control with encoder.
Functions
Low speed operation command
Remote setting (setting clear)
Middle speed operation command
Remote setting (deceleration)
High speed operation command
Remote setting (acceleration)
164
Related Parameters
Pr. 4 to Pr. 6, Pr. 24 to Pr.
27, Pr. 232 to Pr. 239
Pr.59
Pr. 4 to Pr. 6, Pr. 24 to Pr.
27, Pr. 232 to Pr. 239
Pr. 59
Pr. 4 to Pr. 6, Pr. 24 to Pr.
27, Pr. 232 to Pr. 239
Pr.59
Pr. 44 to Pr. 50, Pr. 450 to
Pr. 457, Pr. 463
Pr. 15, Pr. 16
Pr. 4 to Pr. 6, Pr. 24 to Pr.
27, Pr. 232 to Pr. 239
Pr. 110, Pr. 111, Pr. 116
Pr. 79
Pr. 128 to Pr. 134
Pr. 278 to Pr. 285
Pr. 79
Pr. 29, Pr. 380 to Pr. 383
Pr. 350 to Pr. 369
Pr. 802
Pr. 17
Pr. 815
STR terminal (Pr. 187) only
(Note) DI1 to DI4 functions
are made invalid.
Response
Time
Within 20ms
Within 20ms