Mitsubishi Electric FR-V560 Instruction Manual page 51

Vector inverter
Table of Contents

Advertisement

Using the second motor
Param
Name
eter
Second motor
453
capacity
Number of second
454
motor poles
Rated second motor
456
voltage
Rated second motor
457
frequency
Second auto tuning
463
setting/status
Turn on/off the RT signal to switch between the first and second motors using contacts information of the
magnetic contactor (MC).
(Use the RT signal after setting it to any of the DI1 to DI4 signals using Pr. 180 to Pr. 183, Pr. 187 (input terminal
function selection).
By setting values other than "9999" in Pr. 451 when Pr. 450="9999" (factory setting), the control system of the first
motor can be changed by switching the RT terminal on and off.
(In this case, turning the RT signal on makes the second function of Pr. 44, Pr. 45, Pr. 452, Pr. 456, Pr. 457, Pr. 463,
and Pr. 830 to Pr. 837 valid.
Factory
Setting
Inverter
Set the motor capacity.
capacity
0.4 to 55kW (0.5 to 75HP)
Set the number of motor poles.
4
2, 4, 6P
Set the rated voltage
575V
0 to 100V
Set the rated frequency
60Hz
20 to 200Hz
0
: Without auto tuning
0
1
: Tuning without running the motor
101 : Tuning with running the motor
Setting Range
42
Setting can
be made
when
Pr. 450
"9999"