Mitsubishi Electric FR-V560 Instruction Manual page 210

Vector inverter
Table of Contents

Advertisement

<Operation procedure>
• When operation panel (FR-DU04
1) Select the PU operation mode.
2) Set the speed.
SET
3) Press
4) Read Pr. 900 "DA1 terminal calibration" or Pr. 901 "DA2 terminal calibration".
FWD
5) Press
6) Hold down
(Depending on the setting, the needle may take some time to move.)
SET
7) Press
8) Press
REMARKS
Calibration can also be made for external operation. Set the speed in the external operation mode and make calibration as in
steps 4) to 8).
CAUTION
1. Calibration can be made even during operation.
2. Refer to the FR-PU04V instruction manual for the operation procedure using the parameter unit
(FR-PU04V).
Related parameters
• Pr. 54 "DA1 terminal function selection" (Refer to page 110.)
• Pr. 55 "speed monitoring reference" (Refer to page 113.)
• Pr. 56 "current monitoring reference" (Refer to page 113.)
• Pr. 158 "DA2 terminal function selection" (Refer to page 110.)
-1
) is used
.
to run the inverter. (Motor need not be connected during V/F control.)
to adjust the meter needle to a required position.
for about 1.5s.
STOP
to stop the inverter.
RESET
Calibration functions (Pr. 900 to Pr. 920)
201
4