4.11.5 Reset selection/disconnected PU detection/PU stop selection
with
Encoder
(Pr. 75
Speed
You can select the reset input acceptance, PU (FR-DU04-
function and PU stop function.
Reset selection:
Disconnected PU detection: When the disconnection of the PU (FR-DU04-
PU stop selection:
Parameter
Reset selection/disconnected PU
75
detection/PU stop selection
<Setting>
Pr. 75
Reset Selection
Setting
0
Reset input is always enabled.
Reset input is enabled only when the
1
protective function is activated.
2
Reset input is always enabled.
Reset input is enabled only when the
3
protective function is activated.
14
Reset input is always enabled.
Reset input is enabled only when the
15
protective function is activated.
16
Reset input is always enabled.
Reset input is enabled only when the
17
protective function is activated.
(1) Restarting method when stop was made by inputting
(Method of restarting from
1) After the motor has decelerated to a stop, turn off the STF or STR signal.
MODE
2) Press
twice* to display
CAUTION
When Pr. 79 = "3", press
(*For monitor screen)
.......
3) Press
SET
.
4) Turn on the STF or STR signal.
REMARKS
• When you provide a reset input (RES) during operation, the inverter that is being reset shuts off the output and resets the
internal heat integrating value of the electronic thermal relay function and the number of retries, and the motor coasts.
• The Pr. 75 value can be set any time. This value does not return to the initial value even if parameter (all) clear is executed.
• When the motor is stopped from the PU,
without
with
without
Condi-
tional PLC
Encoder
Encoder
Encoder
Torque
Position
You can select the reset function input (RES signal) timing.
more than 1s is detected, the inverter outputs an alarm code (E.PUE) and
comes to an alarm stop.
When an alarm etc. occurs in any operation mode, you can stop the motor from
the operation panel by pressing
Name
Disconnected PU
If the PU is disconnected,
operation will be continued
as-is.
When the PU is
disconnected, the inverter
output is shut off.
If the PU is disconnected,
operation will be continued
as-is.
When the PU is
disconnected, the inverter
output is shut off.
indication)
.
MODE
three times to display
Refer to the Instruction Manual (basic) for details of the monitor display provided
by pressing
MODE
.
and
are displayed alternately. An alarm output is not provided.
Operation selection function 2 (Pr. 65 to Pr. 79)
SSC
)
1
/FR-PU04V) connector disconnection detection
1
/FR-PU04V) from the inverter for
STOP
.
RESET
Factory
Setting Range
Setting
14
0 to 3, 14 to 17
Detection
The PU stop key is invalid.
input is valid only in the PU or combined
operation mode (Pr. 79 = "4").
STOP
RESET
to a stop in any of the PU, external and
communication operation modes.
STOP
RESET
. Then press
and proceed to 3).
127
Remarks
Extended mode
PU Stop Selection
STOP
RESET
input decelerates the motor
from the operation panel
4

Advertisement