Communication functions (Pr. 117 to Pr. 124)
<Setting>
To make communication between the personal computer and inverter, the initial settings of the communication
specifications must be made to the inverter. Data communication cannot be made if the initial settings are not made
or there is any setting error.
CAUTION
Always reset the inverter after making the initial settings of the parameters. Communication is disabled
unless the inverter is reset after the communication-related parameter values have been changed.
Parameter
Name
Number
Communication
117
station number
Communication
118
speed
Stop bit length/
119
data length
Parity check
120
presence/
absence
Number of
121
communication
retries
Communication
122*
check time
interval
Waiting time
123
setting
CR/LF
instruction
124
presence/
absence
* When making communication, set any value other than 0 in Pr. 122 "communication check time interval".
Factory
Setting
Setting
Station number specified for communication from the PU connector.
0
0 to 31
Set the inverter station numbers when two or more inverters are
connected to one personal computer.
48
4800bps
192
96
9600bps
192
19200bps
0
Stop bit length 1 bit
8
bits
1
Stop bit length 2 bits
1
10 Stop bit length 1 bit
7
bits
11 Stop bit length 2 bits
0
Absent
2
1
Odd parity present
2
Even parity present
Set the permissible number of retries at occurrence of data receive
0 to 10
error. If the number of consecutive errors exceeds the permissible
value, the inverter will come to an alarm stop (E. PUE).
If a communication error occurs, the inverter will not come to an alarm
1
stop. At this time, the inverter can be coasted to a stop by MRS or
9999
RESET input.
(65535)
During a communication error (H0 to H5), the minor fault signal (LF) is
given to the open collector output. Allocate the used terminal with any
of Pr. 190 to Pr. 192 and Pr. 195 (output terminal function selection).
0
No communication
Set the communication check time [s] interval.
0.1 to
9999
If a no-communication state persists for longer than the permissible
999.8s
time, the inverter will come to an alarm stop (E. PUE).
9999
Communication check suspension
0 to
Set the waiting time between data transmission to the inverter and
150ms
response.
9999
9999
Set with communication data.
0
Without CR/LF
1
With CR
1
2
With CR/LF
142
Description