Selection Of Peripheral Devices - Mitsubishi Electric FR-V560 Instruction Manual

Vector inverter
Table of Contents

Advertisement

1.1.2

Selection of peripheral devices

Check the motor applicable to the inverter you purchased. Appropriate peripheral devices need to be selected
according to the motor capacity. Refer to the list below and prepare appropriate peripheral devices.
Motor Output
Applicable
(kW (HP))
Inverter Type
2.2 (3)
FR-V560-2.2K-NA
3.7 (5)
FR-V560-3.7K-NA
7.5 (10)
FR-V560-7.5K-NA
15 (20)
FR-V560-15K-NA
22 (30)
FR-V560-22K-NA
37 (50)
FR-V560-37K-NA
55 (75)
FR-V560-55K-NA
* • Select the NFB type according to the power supply capacity.
• Install the NFB according to the inverter capacity.
• When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage of the inner
parts of the inverter, etc. Identify the cause of the trip, then remove the cause and power on the breaker.
• For installation in the United States and Canada, select circuit breakers authorized by UL and cUL.
Basic configuration and connection
No-fuse Breaker (NFB) or
Earth Leakage Circuit Breaker (ELB)
With power factor
Standard
improving reactor
15A
20A
30A
60A
90A
150A
200A
3
of peripheral devices
*
Fuse
10A
K5-15A
15A
K5-20A
30A
K5-40A
50A
K5-80A
75A
K5-110A
125A
K5-200A
175A
K5-300A
Magnetic
Contactor
(AC3)
7A
10A
21A
42A
59A
94A
137A
1

Advertisement

Table of Contents
loading

Table of Contents