MX240 3D Universal Edge Router Hardware Guide

MX240 Router Cabinet Airflow Requirements

Related
Documentation

Installing an MX240 Router Overview

110
Before you install the router in a cabinet, you must ensure that ventilation through the
cabinet is sufficient to prevent overheating. Consider the following requirements to when
planning for chassis cooling:
Ensure that the cool air supply you provide through the cabinet can adequately dissipate
the thermal output of the router.
Ensure that the cabinet allows the chassis hot exhaust air to exit from the cabinet
without recirculating into the router. An open cabinet (without a top or doors) that
employs hot air exhaust extraction from the top allows the best airflow through the
chassis. If the cabinet contains a top or doors, perforations in these elements assist
with removing the hot air exhaust. For an illustration of chassis airflow, see
Figure 40 on page
110.
Install the router as close as possible to the front of the cabinet so that the cable
manager just clears the inside of the front door. This maximizes the clearance in the
rear of the cabinet for critical airflow.
Route and dress all cables to minimize the blockage of airflow to and from the chassis.

Figure 40: Airflow Through the Chassis

MX240 Router Clearance Requirements for Airflow and Hardware Maintenance on
page 108
MX240 Router Cabinet Size and Clearance Requirements on page 109
To install the MX240 router:
Prepare your installation site as described in
1.
page
105.
Review the safety guidelines and warnings.
2.
"MX240 Site Preparation Checklist" on
Copyright © 2016, Juniper Networks, Inc.