MX240 Site Preparation Checklist
Table 58: Site Preparation Checklist
Item or Task
Verify that environmental factors such as
temperature and humidity do not exceed router
tolerances.
Select the type of rack or cabinet.
Copyright © 2016, Juniper Networks, Inc.
Table 57: Routers Environmental Specifications
Description
Altitude
Relative humidity
Temperature
Seismic
Maximum thermal output
NOTE:
Install the router only in restricted areas, such as dedicated equipment
rooms and equipment closets, in accordance with Articles 110-16, 110-17, and
110-18 of the National Electrical Code, ANSI/NFPA 70.
Routine Maintenance Procedures for the MX240 Router on page 353
General Safety Guidelines for Juniper Networks Devices on page 413
General Safety Warnings for Juniper Networks Devices on page 414
Compliance Statements for Environmental Requirements for Juniper Networks Devices
on page 454
The checklist in
Table 58 on page 105
preparing a site for router installation.
For More Information
"MX240 Router Environmental
Specifications" on page 104
"MX240 Router Rack Requirements"
on page
"MX240 Router Cabinet Size and
Clearance Requirements" on page 109
Value
No performance degradation to 10,000 ft (3048 m)
Normal operation ensured in relative humidity range of 5% to 90%,
noncondensing
Normal operation ensured in temperature range of 32°F (0°C) to
104°F (40°C)
Nonoperating storage temperature in shipping container:
–40°F (–40°C) to 158°F (70°C)
Designed to meet Telcordia Technologies Zone 4 earthquake
requirements
AC power: 7161 BTU/hour (2100 W)
DC power: 5074 BTU/hour (1488 W)