90 Clearing faults
Condition
Data dump error, or
no access to overlays
while OVL005 message
is displayed
Red LED is lit on SSC
card
Red LED is lit on SSC
card
Copyright © 2007, Nortel Networks
.
Possible cause
Manual initialize button
pressed when performing
a backup using the
Customer Configuration
Backup and Restore
feature
Card circuitry latched
Improperly installed
NTTK25 software
daughterboard
Defective NTTK25
software daughterboard
Improperly installed
NTDK83 IP
daughterboard
Defective NTDK83 IP
daughterboard
Defective NTDK20 SSC
card
Nortel Communication Server 1000
Communication Server 1000E Maintenance
NN43041-700 01.02 Standard
Release 5.0 20 June 2007
Action
Issue the ENLT command at the TTY.
Disable the SSC card. Unseat and reseat
the card and then reenable it. If the fault
persists, go to the next possible cause.
Power down the system and remove the
NTDK20 SSC card.
Unseat and reseat the software
daughterboard.
Reinsert the NTDK20 SSC circuit card.
Power up the system.
Unseat the NTDK20 SSC circuit card and
replace the software daughterboard.
Reinsert the NTDK20 SSC circuit card.
Power down the system and remove the
NTDK20 SSC card.
Unseat and reseat the IP daughterboard.
Reinsert the NTDK20 SSC circuit card.
Power up the system.
Unseat the NTDK20 SSC circuit card and
replace the IP daughterboard.
Reinsert the NTDK20 SSC circuit card.
If the fault persists, replace the NTDK20
SSC card. Reuse all daughterboards and
the security device installed on the original
NTDK20 SSC circuit card.
Enable and test the card by entering:
LD 30
TEST
If the new card passes the test, the original
NTDK20 SSC circuit card was defective.
If after a few minutes the problem reoccurs,
replace the Media Gateway.