126 Replacing equipment
2
3
4
5
6
7
8
9
10
11
12
Copyright © 2007, Nortel Networks
.
In LD 135, split the CPU cores:
SPLIT
Remove all cables connected to the CPU being replaced.
Use a small-bladed screwdriver to remove the screws from the CP
PIV card.
To remove the card, hold the card by the faceplate latches and gently
pull it out of the slot.
To install the replacement card, hold the card by the faceplate
latches and gently push it into the slot until the connectors make
contact with the backplane.
Gently push the latches forward to set the card and lock it in place.
CAUTION
Damage to Equipment
Never force the card into the slot. It the card gets stuck,
remove it and try again.
Use a small-bladed screwdriver to replace the screws on the card.
Replace all cables on the replaced CP PIV card.
Before continuing with this procedure, you must reinstall the software from
Compact Flash. See "Installing software" procedures in Communication
Server 1000M and Meridian 1: Large System Installation and
Configuration (553-3021-210), Release 4.5.
After the inactive Call Server reloads, check status in LD 135:
STAT CPU
In LD 135, on the active Call Server, rejoin the two CP PIV cards:
JOIN
After the disk sync and memory sync complete, enter the following
in LD 135:
STAT CPU
Nortel Communication Server 1000
Communication Server 1000E Maintenance
NN43041-700 01.02 Standard
Release 5.0 20 June 2007
ATTENTION
To check for normal system operation.