Commissioning and configuring
6.5 Configuring NC and drive-specific safety settings
Setting
Fault tolerance
Speed tolerance
262
Meaning
Setting of the plausibility monitoring tolerance for the current and the volt‐
age angle.
A higher value makes the drive more stable when it is reversing at low
speeds - or when the load changes abruptly in the field-weakening range.
An increase brings advantages when the current or voltage at the motor
becomes small.
Increasing the value results in a longer evaluation delay - and to a higher
speed tolerance (see below).
Notice: Reducing this value can have a negative impact on the actual value
acquisition and the plausibility check.
For synchronous motors, the value must be set to 4.
For value = -1:
- for synchronous motors, the calculation automatically uses a value of 4
- for induction motors, the calculation automatically uses a value of 0 (if the
code number of the power unit p0201[0] is < 14000, otherwise a value of
2 is used).
Dependencies: F01681, C01711
Displays the actual speed deviation for encoderless actual value acquisi‐
tion.
This value is calculated when setting the error tolerance (see above).
Safety Integrated (with SINAMICS S120)