Safety functions integrated in the drive
4.6 SS2
How does SS2 function in detail?
The failsafe logic (e.g. F‑PLC) selects the SS2 safety function via a failsafe input or via the
PROFIsafe safe communication.
● If, when selecting SS2, the motor is already at a standstill, after a delay time, the converter
activates the Safe Operating Stop function (SOS).
● If the drive is not at standstill when SS2 is selected, it is braked along the OFF3 ramp.
Braking is monitored with one of the following functions, depending on the setting in p9506:
– Safe Acceleration Monitor (SAM)
– Safe Brake Ramp (SBR)
After a delay time, the converter activates the Safe Operating Stop function (SOS). This
function monitors the safe standstill of the drive.
Braking behavior
Figure 4-5
116
A faulty acceleration is therefore detected.
In this way, a violation of the braking ramp is detected.
Braking behavior and diagnostics (example for SS2 with SAM)
Safety Integrated (with SINAMICS S120)