Controlling safety functions integrated in the drive
5.4 Control via PROFIsafe
5.4.3

ESR response in the event of a communication error

The response of the SINAMICS S120 drive in the case of a communication error when the
"Extended stop and retract (ESR)" function module is simultaneously enabled is described in
the following.
Requirement
● The Safety Integrated Extended Functions are controlled via PROFIsafe
● The function module "Extended stop and retract" is activated and enabled
Communication failure
Under communication failure in this context, we understand one of the following possibilities:
● Interruption/fault of the PROFINET connection for control via PROFIsafe
● STOP response of the F-PLC
Drive response
In the event of a communication failure, SINAMICS S120 makes a distinction between the
following responses:
● If p9580 ≠ 0 and ESR has been enabled, in the event of a communication failure, the
parameterized ESR response is realized.
● If p9580 ≠ 0 and SLS is active, in the event of communication failure, the parameterized ESR
reaction is only realized if, as SLS response, a STOP with delayed pulse cancellation when
the bus fails has been parameterized (p9563[0...3] ≥ 10).
● If p9580 ≠ 0 and SDI is active, in the event of communication failure, the parameterized ESR
reaction is only realized if, as SDI response, a STOP with delayed pulse cancellation when
the bus fails has been parameterized (p9566[0...3] ≥ 10).
● If p9580 ≠ 0 and SLP is active, in the event of communication failure, the parameterized ESR
reaction is only realized if, as SLP response, a STOP with delayed pulse cancellation when
the bus fails has been parameterized (p9562[0...1] ≥ 10).
Note
Maximum response time for interruption in communication
When a safety-relevant communication is interrupted, Safety Integrated only permits a
response time (p9580) of max. 800 ms. The drive changes into the "fail safe state" once this
time expires. In this case, S_STW1/2 is assumed to be 0. This means that all safety functions
are selected. STO has in this case the highest priority, i.e. the pulses are safely canceled.
210
Safety Integrated (with SINAMICS S120)